Do you want to view the programmable timer settings?
CE1B3058en / 17.11.2005 Subject to alteration Building Technologies / HVAC Products
Do you want to reload the default timer settings?
+
1.
Set the controller to standby .
2. Press and simultaneously for 3 seconds. Release them and, within 2
seconds, press 2 times
.
Day/s
Time when controller is in normal operation
Mo (1) – Fr (5) 06:30 – 08:30 (A1) 17:30 – 22:30 (A2)
Sa (6) 08:00 – 23:00 (A3)
Su (7) 08:00 – 22:30 (A4)
Default
settings
- in the remaining time controller is in energy saving
- timer A5…A8 are free, no default setting
Changing the control parameters
To optimize the control performance, a number of control parameters can be adjusted. This can
also be made during operation without opening the controller.
If you want to change the control parameters, proceed as follows:
(For factory settings, see table on the right-hand side)
+
/
+
+
1. Set the controller to standby
2. Press
and simultaneously for a minimum of 3 and a
maximum of 5 seconds. Release them and, within 2 seconds, press
the
again for 3 seconds. The display will show “P01”.
3. Select the required parameter by repeatedly pressing the
or button:
P01 P02 P22 P98
+-+
--
+
3057z03
P99
-
+
-
P25
+-
4. Press
and simultaneously. The current value of the selected
parameter will appear, which can be changed by repeatedly pressing
or .
5. By pressing
and simultaneously again or 5 seconds.
after the last press of a button, the last parameter will be displayed
again.
6. If you wish to display and change additional parameters,
repeat steps 3 through 5.
7. 10 seconds after the last display or setting, all changes are
stored and the controller will return to standby.
8. Switch to normal operation with the button.
Recalibrating the sensor
If the room temperature displayed by the controller does not agree with the temperature effectively
measured, the temperature sensor can be recalibrated. For that purpose parameter P07 must be
changed.
Proceed as described under “Changing the control parameters” and follow steps
1 through 3 to select parameter P07.
With step 4, the room temperature displayed can now be matched to the
temperature effectively measured. Each push of the
or button changes
the temperature by + or – 0.5 °C up to a maximum of + / - 3 °C.
With step 7, the recalibration is automatically stored 10 seconds after the last
readjustment.
Commissioning (by qualified HVAC staff) (all temperature settings can be made in increments of 0.5 K)
Para-
meter
Controller’s parameter factory settings: Setting range RDF210 RDF210.2
P01 Setpoint of heating in energy saving mode (Wheat
Eco
) 16 OFF, 5 °C…Wcool
Eco
P02 Setpoint of cooling in energy saving mode (Wcool
Eco
) 28 OFF, Wheat
Eco
…40 °C
P03
Setpoint of heating in standby
(Wheat
Stb
)
OFF OFF, 5 °C…Wcool
Stb
P04
Setpoint of cooling in standby
(Wcool
Stb
)
OFF OFF, Wheat
Stb
…40 °C
P05 Minimum setpoint limitation in normal operation (Wmin
Norm
) 5 °C 5 °C…Wmax
Norm
P06 Maximum setpoint limitation in normal operation (Wmax
Norm
) 35 °C
Wmin
Norm
…40 °C
P07 Sensor calibration 0 K
-3…+3 K
P08 Switching differential heating SDH 2 K
0.5…+4K
P09 Switching differential cooling SDC 1 K
0.5…+4K
P10 Switching differential fan speed 2 in heating operation mode SDH2 1 K
0.5…+4K
P11 Switching differential fan speed 2 in cooling operation mode SDC2 1 K
0.5…+4K
P12 Switching differential fan speed 3 in heating operation mode SDH3 1 K
0.5…+4K
P13 Switching differential fan speed 3 in cooling operation mode SDC3 1 K
0.5…+4K
P14 Dwelling time of auto fan speeds 2 min.
1…5 minutes
P15 Minimum output on-time (Y11) 1 min.
1…10 minutes
P16 Minimum output off-time (Y11) 1 min.
1…10 minutes
P17 Selection of °C or °F °C °C or °F
P18 Display of temperature or setpoint ON
OFF: Setpoint
ON: Room (or return air)
temperature
P20 Fan control in energy saving mode OFF
OFF in dead zone
ON in dead zone
P21 Fan control in normal operation OFF
OFF in dead zone
ON in dead zone
P22 Heating / cooling mode
1:
Cooling
only
0: Heating only
1: Cooling only
2: Automatic c/h changeover
X
P23 Heating / cooling changeover switching point cooling 16°C 10…25 °C
X
P24 Heating / cooling changeover switching point heating 28°C 27…40 °C
X
P25 Infrared receiver (only with RDF.../IR) 1
0: Disabled
1: Enabled
P98 Active temperature sensor
Diagnostic
value
0: Internal sensor
1: External sensor
P99
Value of current heating / cooling changeover temperature
reading or indication of current mode
Diagnostic
value
100 = input open Æ mode
0…49 °C = cur. temp. value
00 = input bridged Æ
mode
OFF= not commissioned as
automatic c/h changeover
X
Press the button to sequentially review the 8 auto timers.
Legend to table
Adjustable: Please record all changes you make
Not adjustable / display only
X
Not adjustable / no display
2


Need help? Post your question in this forum.

Forumrules
1

Forum

siemens-rdf-210

Reset search

  • Bonjour mon thermostat ne s’allume plus il n’y a plus rien d’affiché du coup mes radiateurs ne se mettent pas en route et j’ai très froid. Comment puis je le rallumer ?
    Merci Submitted on 4-12-2021 at 10:54

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDF 210 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDF 210 in the language / languages: English as an attachment in your email.

The manual is 0,51 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDF 210

Siemens RDF 210 User Manual - German - 2 pages

Siemens RDF 210 User Manual - French - 2 pages

Siemens RDF 210 Installation Guide - All languages - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info