CE1G2206xx 2015-03-18 9/56
Configuration and function check REV24RF..
1 Configuration
1.1 DIP switches
ON / OFF 1 2 3 4 5 6 7 8 9 10
See
See 1.1.1
Sensor calibration on
Periodic pump run on
1.1.5
Sensor calibration off Periodic pump run off
1.1.2
Setpoint limitation 16…35 °C
Optimum start control:1 h/°C
1.1.6
Setpoint limitation 3…35 °C Optimum start control: ¼ h/°C
1.1.3
Temperature display °F
Optimum start control: ½ h/°C
Temperature display °C Optimum start control: Off
1.1.4
PID self-learning
(Cooling on)
1.1.7
PID 6
(Heating on)
PID12 Quartz
1.1.8
2-Point
Radio clock
1.1.9 DIP switch reset
ON
1 342
2211Z32
56 7 89
When changing one or several DIP switch positions, a DIP switch reset must be made by pressing the DIP switch reset button (also refer to Fig.
8). Otherwise, the previous settings will be maintained!
1.1.9
Note: The factory setting of all DIP switches is OFF
1.1.1 Sensor calibration: DIP switch 1
Set the DIP switch to ON and press the DIP switch reset button:
The display shows CAL. The room temperature currently acquired blinks.
Press
or to make a recalibration of max. ± 5 °C. To save the entry,
set the DIP switch to OFF and press the DIP switch reset button (also refer to
Fig. ).
1.1.2 Setpoint limitation: DIP switch 2
DIP switch ON: Setpoint limitation 16…35 °C
DIP switch OFF: Setpoint limitation 3…35 °C
(factory setting)
Save the entry by pressing the DIP switch reset button.
1.1.3 Temperature display in °C or °F:
DIP switch 3
DIP switch ON: Temperature display in °F
DIP switch OFF: Temperature display in °C
(factory setting)
Save the entry by pressing the DIP switch reset button (also refer to Fig.
).
1.1.4 Control action: DIP switches 4 and 5
DIP switch 4 ON and 5 ON: PID self-learning
Adaptive control for all types of application.
DIP switch 4 ON and 5 OFF: PID 6
For fast controlled systems, applications at locations with great
temperature variations.
DIP switch 4 OFF and 5 ON: PID 12
For normal controlled systems, applications at locations
with normal temperature variations.
DIP switch 4 OFF and 5 OFF: 2-Point
For difficult controlled systems, 2-position controller with
a switching differential of 0.5 °C (factory setting).
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.5 Periodic pump run: DIP switch 6
Can only be used when circulating pump or valve is controlled!
This function protects the pump or valve against seizing during longer off
periods. Periodic pump run is activated for 3 minutes every 24 hours at 12:00
(display showing symbol ).
DIP switch ON: Periodic pump run on (also refer to Fig. )
DIP switch OFF: Periodic pump run off (factory setting)
Save the entry by pressing the DIP switch reset button.
1.1.6 Optimum start control: DIP switches 7 and 8
Optimum start control shifts switch on point P.1 such that the adjusted setpoint
will be reached at the required point in time. The setting depends on the type of
controlled system, that is, on heat transmission (piping network, radiators),
building dynamics (building mass, insulation) and heat output (boiler output,
flow temperature)
(also refer to graph in Fig.
/ 1.1.6).
DIP switch 7 ON and 8 ON: 1 h/°C For slow controlled systems
DIP switch 7 ON and 8 OFF: ¼ h/°C For fast controlled systems
DIP switch 7 OFF and 8 ON: ½ h/°C For medium controlled systems
DIP switch 7 OFF and 8 OFF: OFF Off, no impact (factory setting)
Save the entry by pressing the DIP switch reset button.
Legend to graph in Fig. .
.:
t Temperature (°C)
t Forward shift of switch on point (h)
TRx Actual value of room temperature
Pon Start point for optimum start control
1.1.7 Heating or cooling mode: DIP switch 9
DIP switch 9 ON:
Cooling
DIP switch 9 OFF:
Heating mode (factory setting)
Save the entry by pressing the DIP switch reset button
(also refer to Fig. ).
1.1.8 Radio clock: DIP switch 10
Can only be used if receiver DCF77 is integrated (time signal from Frankfurt)!
DIP switch ON: Clock runs on built-in quartz
DIP switch OFF: Time signal DCF77 from Frankfurt
Save the entry by pressing the DIP switch reset button
(also refer to Fig. ).
1.1.9 DIP switch reset (Fig. )
When changing one or several DIP switch positions, press the DIP switch reset
knob to make a DIP switch reset.
Otherwise, the previous settings will be maintained!
(Also refer to Fig. )
2 Accessing the expert level
Move the selector slider to the RUN position and press simultaneously
and for 3 seconds, then release the buttons and, within 3 seconds, press
simultaneously and for 3 seconds, release and keep depressed for another 3 seconds. This enables you to access the expert level for making the
settings on that level. on display (also refer to Fig. G).
Starting with code 00, the display shows the choice of languages. Navigation on the expert level is made possible with
and . Confirm the settings by
pressing .
DE
EN
FR
IT
NL
ES
PT
CS
HU
PL
SV
FI
DA
TR
EL
RO
9


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RCR10-868 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RCR10-868 in the language / languages: All languages as an attachment in your email.

The manual is 1,5 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RCR10-868

Siemens RCR10-868 User Manual - English - 2 pages

Siemens RCR10-868 User Manual - German - 2 pages

Siemens RCR10-868 User Manual - French - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info