Siemens Schweiz AG User Manual CE1U2354en
HVAC Products QAA75.. / QAA78… / AVS37.. 23. August 2007
Operating line
User level
Function
Default value
Min
Max
Unit
732 F 24-hour heating limit -3 / -10 10 °C
740 I Flow temp setpoint min 8 8 Operating line 741 °C
741 I Flow temp setpoint max 80 Operating line 740 95 °C
750 F Room influence 20 / 1 100 %
760 F Room temp limitation 1 / 0.5 4 °C
770 F Boost heating 5 / 0 20 °C
780 F Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot spt
Down to reduced setpoint
-
790 F Optimum start control max 0 0 360 min
791 F Optimum top control max 0 0 360 min
800 F Reduced setp increase start / -30 10 °C
801 F Reduced setp increase end -15 -30 Operating line 800 °C
820 F
Overtemp prot pump circuit
Off ¦ On
On
-
830 F Mixing valve boost 5 0 50 °C
832 F
Actuator type
2-position ¦ 3-position
3-position
-
833 F Switching differential 2-pos 2 0 20 °C
834 F
Actuator running time
120 30 873 s
850 I Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦ Functional
/curing heating¦ Curing/functional heating ¦ Manually
Off
-
851 I Floor curing setp manually 25 0 95 °C
861 F Excess heat draw
Off ¦ Heating mode ¦ Always
Always
870 F With buffer storage tank
No ¦ Yes
Yes
-
872 F With primary controller / system pump
No ¦ Yes
Yes
882
6)
F Pump speed min 100 0 100 %
883
6)
F Pump speed max 100 0 100 %
900 F Changeover of operating mode
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic
Protection mode
Cooling circuit 1
901
4)
E Operating mode
Off ¦ Automatic
Automatic
-
902
4)
E Comfort cooling setpoint 24.0 15 40 °C
907
4)
E
Enable
24h/day ¦ Time programs HCs ¦ Time program 5
24h/day
-
908
4)
I
Flow temp. setpoint at OT 25°C
20 8 35 °C
909
4)
I
Flow temp. setpoint at OT 35°C
16 8 35 °C
912
4)
I
Cooling limit at OT
20 / 8 355 °C
913
4)
F
Locking period at end of heating
24 / 8 100 h
918
4)
F
Start of summer compensation at OT
26 20 35 °C
919
4)
F
End of summer compensation at OT
35 20 35 °C
920
4)
F
Summer compensation setpoint increase
4 / 1 10 °C
923
4)
I
Flow setpoint min. OT 25°C
18 8 35 °C
924
4)
I
Flow setpoint min. OT 35°C
18 8 35 °C
928
4)
F Room influence 80 / 1 10 %
932
4)
F Room temp limitation 0.5 / 0.5 4 °C
938
4)
F
Mixing valve cooling offset
0 0 20 °C
47


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens QAA 75.611 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens QAA 75.611 in the language / languages: English as an attachment in your email.

The manual is 3,88 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens QAA 75.611

Siemens QAA 75.611 Installation Guide - German - 136 pages

Siemens QAA 75.611 User Manual - German - 64 pages

Siemens QAA 75.611 User Manual - French - 180 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info