668968
24
Zoom out
Zoom in
Previous page
1/94
Next page
22
Building Technologies A6V10393190_c_en_--
Fire Safety
2014-05-28
4.3.2
Mixed
The mixed line allows a mixture of detectors and manual call points within the same
zone. Moreover it can distinguish between direct and delayed alarming.
Technical:
- Siemens detectors 110-series or detectors with an alarm resistor are required for
delayed alarming (AVC, V1 / V2).
- MCPs require a Z-diode for direct alarming (AVC).
- Max. 32 devices on each line.
- Each line must be terminated with EOL element Transzorb diode (18 V TVS).
Programming:
- Configure
Zone
Zone 1 – n
Mode
Mixed MCP & det.
- Configure
Zone
Zone 1 – n
AVC
Via AVC timer MCP direct
Zone mode 'Mixed' does NOT comply with EN 54-13.
Behavior of MCP in zone coincidence with function 'direct alarming' is not supported
.
24


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens FC124-ZA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens FC124-ZA in the language / languages: English as an attachment in your email.

The manual is 3,88 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info