Building Technologies A6V10393190_c_en_--
Fire Safety
2014-05-28
3.4
Standard and options EN 54
The fire control panel is designed to comply with the requirements of EN 54 part 2 / 4.
EN 54-2 Definitions
The EN 54-2 options are fulfilled if the following
configurations are used.
Installation Configuration / Operation Chapter
7.8 Output to fire alarm device
EN 54-1 / C
Monitored output
e.g. OUT 1
Sounder control
7.1.2
6.4.2
7.2.6
7.9.1 Output to fire alarm routing equipment
EN 54-1 / E
Monitored output
e.g. OUT 2
Alarm dialer 7.1.2
7.2.4
7.9.2 Alarm confirmation input from fire
alarm routing equipment
Input Dialer device confirmation
signal; LED fire brigade
activated via input
7.1.3
7.2.4
7.10.1 Outputs to fire protection equipment
EN 54-1 / G
Monitored output
e.g. OUT 4
Fire output 7.1.2
7.11.1 Delays to outputs V1 / V2 timer for
alarm organization
Alarm Verification Concept;
Manned / unmanned
6.1.3
7.2.10
7.11.2 Switch on /off delays to outputs, V1 /
V2 timer for alarm organization
Button 'Manned/unmanned' 6.4.1
7.2.10
7.12.1 Dependencies on more than one
alarm signal.
Type A dependency from the same
detector, or another in the same zone
Detector coincidence inhibit
time 15 - 60 sec.
Reset of the first alarm after
90 sec.
7.1.1
7.2.5
7.12.2 Dependencies on more than one
alarm signal
Type B dependency cross zoning
Zone coincidence
(= cross zoning)
7.1.1
7.13 Alarm counter
(option with requirement)
Alarm counter 6.3.3
7.4
8.8 Output to fault warning routing
equipment
Relay output
e.g. OUT 3
Fault dialer 7.1.2
8.9 Output to fault warning routing
equipment according EN 54-1 / J
Monitored output
e.g. OUT 4
Fault dialer 7.1.2
10 Test condition
(option with requirements)
Test zone 6.4.8
EN 54-13 Definitions
The EN 54-13 standard is achieved, if the following
system functions are fulfilled:
Installation Chapter
5.3.4.2 Open and short circuit on a
transmission path
Zone mode 'standard' 7.1.1
Outputs card supervised
Card 1, OUT A / B: 4 / 5
Card 2, OUT A / B: 8 / 9
Card 3, OUT A / B: 12 / 13
4.4.2
7.1.2
Fault dialer
Card 1, OUT A: 4
Card 2, OUT A: 8
4.4.4
18


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens FC124-ZA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens FC124-ZA in the language / languages: English as an attachment in your email.

The manual is 3,88 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info