6.1.2
Alarm Verification Concept (AVC)
The graphic
below
procedure.
The AVC
Manned operation
Manned operation enables the responsible personnel to examine the fire alarm before
initiating the intervention force. This may avoid hassle
Reaction time (V1)
In case of a fire incident, the responsible personnel must confirm th
control panel by pressing the acknowledge button
I
nvestigation time V2 starts
expires
and the panel automatically
In the event of a major inci
or <
Manned/Unmanned
'ALARM'
state. (
Investigation time (V2)
During the investigation time V2 the operating personnel may examine the
fire:
In the event of a major incident (emergency), the nearest ‘Manual call point’
or <
Manned/Unmanned
'ALARM' state.
The panel goe
s to
AVC
Manned
State 'ALARM'
Buzzer (re-)activated
Sounder output (re-)activated
State
'
A
LERT
Buzzer activated
Sounder
output activated
Reaction time 'V
Reset:
V1 time out
Fire?
Manned/
unmanned:
Yes
No
No
Alarm Verification Concept (AVC)
below
illustrate
s the difference between the AVC and the DIRECT alarm
The AVC
concept takes the interaction of personnel
into consideration.
Manned operation
Manned operation enables the responsible personnel to examine the fire alarm before
initiating the intervention force. This may avoid hassle
s
in case of false alarms.
Reaction time (V1)
In case of a fire incident, the responsible personnel must confirm th
control panel by pressing the acknowledge button
(ACK).
nvestigation time V2 starts
if activated. If nobody confirms
the alert state, the V1 timer
and the panel automatically
goes to 'ALARM' state.
In the event of a major inci
dent (emergency), the nearest ‘Manua
l call point’
Manned/Unmanned
>
button must be pressed to turn the fire cont
state. (
1
function depends on programming)
Investigation time (V2)
During the investigation time V2 the operating personnel may examine the
In the event of a major incident (emergency), the nearest ‘Manual call point’
Manned/Unmanned
>
button must be pressed to turn the fire control panel into
(
2
function depends on programming)
s to
'ALARM' state if the i
nvestigation is not confirmed within
AVC
Manned
Unmanned
Fire output activated
Alarm dialer
activated (Intervention)
output activated
if programmed
” has started
Ack:
Fire?
Yes
V2
start
Reset:
Manned/
unmanned:
Yes
V2 time out
No
43
s the difference between the AVC and the DIRECT alarm
into consideration.
Manned operation enables the responsible personnel to examine the fire alarm before
in case of false alarms.
In case of a fire incident, the responsible personnel must confirm th
e alert at the fire
the alert state, the V1 timer
l call point’
1
button must be pressed to turn the fire cont
rol panel into
During the investigation time V2 the operating personnel may examine the
location of
In the event of a major incident (emergency), the nearest ‘Manual call point
2
button must be pressed to turn the fire control panel into
nvestigation is not confirmed within
time V2.
DIRECT
Unmanned
activated (Intervention)
45


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens FC123-ZA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens FC123-ZA in the language / languages: English as an attachment in your email.

The manual is 3,88 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info