Building Technologies A6V10393190_c_en_--
Fire Safety
2014-05-28
10
Maintenance
It is assumed that the site was commissioned in accordance with the existing
directives, i.e. all functions have been tested and the site data has been saved or
logged to the table 'site configuration'.
10.1
Preparatory work
Inform the system owner of the scope and expected duration of work.
Disable the following system components as needed:
Alarm transmission (log out on the receiving centre)
Fire controls and sounder lines
Extinguishing stations
10.2
Function test
We recommend the following schedule. However, local regulations have priority.
Function Activity Interval in
years
1 2 5
Zones Activate all automatic detectors and all manual call points. X
Activate a detector or manual call point per zone and verify zone assignment
and if usage is in accordance with regulations.
X
Check all detectors and manual call points for soiling and verify if usage is in
accordance with regulations.
X
Activate a fault, short circuit and open line, for each zone and verify zone
assignment and if usage is in accordance with regulations.
X
Inputs Activate each input and verify if usage is in accordance with regulations. X
Outputs Check sounder controls and all acoustic alarm devices. X
Activate fire outputs and check if usage is in accordance with regulations. X
Activate alarm and fault dialer and check the transmission. X
Alarm
organization
Mode Manned
Activate a detector and manual call point and check the timer
V1
and
V2
and
the transmission of the alarm dialer.
X
Mode Unmanned
Activate a detector and check the transmission of the alarm dialer.
X
Panel Check date and time. X
Check the display and LEDs. X
Check earth connections. X
Activate mains and battery fault condition and verify if usage is in accordance
with regulations.
X
78


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens FC121-ZA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens FC121-ZA in the language / languages: English as an attachment in your email.

The manual is 3,88 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info