For technicians only
Assembly Instructions
Mount the hot water wall storage unit as described in the diagram. Observe the instructions in the text.You will find
the diagrams at the beginning of the manual.
Safety advice
Danger of electric shock!
In the case of a fault, disconnect the voltage supply.
Assembly
Assembly Preparation
Closed Operation
Mount close to the tap from which the most hot water will be extracted. A design proofed safety valve combination is to be
installed. In addition, if water pressure exceeds 0.48 Mpa (4.8 bar), a pressure reducing valve is to be installed and adjusted
accordingly. No shut-off valves may be installed between the safety modules and the reservoir. Discharge from the safety valve
must always be open. The safety valve combination for closed operation must be accredited (design proofed):
Safety valve combination AK030300, i.e. safety valve combinations with pressure reducing valve AK040300 can be mounted
13
Closed water heater
• Only connect the appliance to a correctly earthed electrical socket. Do not use extension
cables.
• Only a prototype-tested diaphragm safety valve may be installed.
• During the heating process, expansion water must drip out of the safety valve outlet.
The outlet pipe of the safety valve must remain open to the atmosphere.
The safety valve prevents excessive pressure from developing in the water heater during the
heating process. Expansion water must be able to drain off via the safety valve.
• Do not block the outlet pipe!
The size of the outlet pipe must suit the fully opened safety valve. The blow-off opening of the
safety valve must remain open to the atmosphere.
The blow-off pipe of the safety group must be installed with a constant decline in a frost-free
room. Regular maintenance and operation of the safety valve are required to remove deposits
and to ensure that the safety valve is not blocked.
The installation instructions of the safety group must be followed.
• A shutoff valve must not be installed between the safety valve and the water heater.
• Supplied stickers:“For reasons of safety, water must come out of the outlet pipe during the
heating period! Do not block!”– attach the stickers to the outlet pipe in a clearly visible
position.
The safety valve must be operated regularly to verify its function and to decalcify the valve.
Open outlet water heater
The water heater is only suitable for use with an open (unpressurised) and a single tap
connection. The warm water outlet is used for pressure compensation and may only be
connected to suitable fittings (Order-No. BZ11114, BZ12411)
The tap outlet must always remain free. Do not use perlators (diffusers) or shower taps.
The instructions for unpressurised (open) water heaters that are used with a spray head must
state that the spray head must be regularly cleaned and water scale removed.
The installation instructions for unpressurised (open) water heaters must state that the water
outlet must only be connected to the specified valves and fittings and NOT to any others.
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens DG30025 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens DG30025 in the language / languages: English, German as an attachment in your email.

The manual is 1,51 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info