CM2N3204E / 1.1999 Siemens Building Technologies
16/20 Landis & Staefa Division
Data point values and measured values can be called up under certain data point
numbers.
The controller is supplied with all values factory-set (bold printing). These factory-
settings are selected such that the controller is suited for the majority of plants.
Each of them can be changed, if required. The factory-set data are stored in non-volatile
memory.
No. Description Range Factory-
setting
1 B9 Frost temperature 50.0...+150.0 °C (Read value)
2 Z Input variable 50.0...+150.0 °C/ (Read value)
0...2000 ppm
3 F91 Common fault relay OFF/On (Read value)
4 E7 Control input 1
1)
OFF/On (Read value)
5 E8 Control input 2
1)
OFF/On (Read value)
6 Y30 Minimum limitation 0...100 % 0 %
7 Fan speed 1/2 1
8 Setpoint pair (Comfort/Economy) Co/Ec Ec
9 Room temperature limit heating 0...30 °C 15 °C
10 Room temperature limit cooling 20...50 °C 30 °C
11 Minimum operating time 00.00...12.00 hh.mm 00.30 hh.mm
12 Room temperature limit 10...50 °C 22 °C
13 Outside temperature limit 5...30 °C 12 °C
14 Delta 1...20 K 5 K
15 Minimum operating time 00.00...12.00 hh.mm 00.30 hh.mm
16 Frost alarm value 2...30 °C 5 °C
17 Standby controller 2...50 °C 25 °C
18 P-band frost protection controller 1...30 K 5 K
19 P-band standby controller 1...200 K 7 K
20 TN standby controller 00.00...10.00 mm.ss 03.00 mm.ss
21 Disabling of fan speed 2 acc.
to outside temperature B4
14)
50...+150 °C 15 °C
22 Delta for heating 1...10 K 4 K
23 Delta for cooling 1...10 K 3 K
24 KE room (cascade authority) 0...20.0 2.0
25 TN 00.00...40.00 mm.ss 08.00 mm.ss
26 P-band heating 1...200 K 20 K
27 TN heating
2)
00.00...10.00 mm.ss 02.30 mm.ss
28 P-band heat recovery 1...200 K 15 K
29 TN heat recovery
2)
00.00...10.00 mm.ss 02.00 mm.ss
30 P-band cooling 1...200 K 15 K
31 TN cooling
2)
00.00...10.00 mm.ss 02.00 mm.ss
32 Switching interval SA 1...100 % of Y20 20 %
33 Switching differential SD 1...100 % of Y20 10 %
34 Starting point 10...50 °C 25 °C
35 End point 10...50 °C 30 °C
36 Delta 10...+10 K 2 K
37 Starting point 30...+20 °C 5 °C
38 End point 30...+20 °C 20 °C
39 Delta 10...+10 K 1 K
40 E1 Fire/smoke A / b A
41 E2 Air flow supervision A / b A
42 E3 Overload pump/electric A / b A
43 E4 Overload chiller A / b A
44 E5 Overload fan A / b A
45 E6 AUX, freely available A / b A
46 B9 Frost alarm A / b A
Data point list for
normal operation
Current measured values
Limitation manipulated variable
Presettings
Unoccupied heating/cooling
mode
Night purging
Setpoints frost protec-
tion/standby controller
Parameters frost protec-
tion/standby controller
Displacement ventilation
Control parameters room
temperature controller
Control parameters supply air
temperature controller
Switching points compressor
Summer compensation
Winter compensation
Alarm priorities
16


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens AEROGYR RWI65.02 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens AEROGYR RWI65.02 in the language / languages: English as an attachment in your email.

The manual is 0,25 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens AEROGYR RWI65.02

Siemens AEROGYR RWI65.02 User Manual - German - 50 pages

Siemens AEROGYR RWI65.02 Usermanual and installation guide - Dutch - 73 pages

Siemens AEROGYR RWI65.02 User Manual - French - 22 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info