32 Doc890/3456CV02B
Fig. 21 Distance between air inlet and fl ue gas outlet
The formation of unwanted condensation must be avoided. In the event that during the heating up
period condensation oc curs, the condensate must be able to ow back to the unit. Inspection of
the air supply and fl ue pipe must be possible.
The connection, exit position and height in relation to possible obstacles must comply with the
applicable national and local standards and regulations (see Supplement).
5.3.5 The Flue system
5.3.5.1 General
The ue pipe connection is at the rear of the appliance and has been designed for direct connec-
tion to a corrosion resisting fl ue pipe.
Condensation forms because of the high boiler ef ciency and the considerable degree of cooling
of the fl ue gasses that takes place against the walls of the fl ue pipe. In order to reduce fl ue gas
condensation as much as possible, the use of a double-walled and insulated fl ue pipe is recom-
mended. Aluminium or stainless steel is strongly recommended. Because a slight overpressure
exists in the fl ue pipe during a cold start-up, fl ue pipes should preferably be constructed from
seamless materi als. When the boiler functions as a high capacity boiler, the high ef ciency can
lead to the formation of condensation in the chimney.
y
The condensate drain must never become blocked!
Direct connection to brick built stacks is not permitted because the combustion ef ciency of the
boiler is › 83 %. The combus tion products at low fl ue gas temperatures will damage the stack.
The following table lists all the fl ue gas data for all types of boiler.
29


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Rendamax R3400 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Rendamax R3400 in the language / languages: English as an attachment in your email.

The manual is 1,8 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info