9 Internal network
Up to 32 units can be operated at the same time
thanks to the parallel connection via a bus line
(accessory). The units can access this network
(internal network) at the same time.
The network can have one leading unit (master)
and up to 31 following units (slave).
The units are connected together via a two-core,
shielded bus line.
The minimum cross section is 1.0 mm
2
with a max-
imum line length of 500 m in the network (observe
the polarity!).
The end of the network must be marked by the
plugged in jumper JP1. The addresses are
assigned by adjusting the DIP switch block SW1
(see the "Configuration" chapter).
Network with infrared remote controls
n The standard infrared remote control operates
a master unit. All slave units are set according
to the programming.
n The infrared remote control or the cabled
remote control (accessory) can be used for
user-specific operation of an individual slave
unit.
Implementation
n Address assignment for the units is carried out
by changing the DIP switch settings for DIP
switch block SW1.
Network with cabled remote controls
n The cabled remote control that is available as
an accessory operates a master unit. All slave
units with cabled remote control can be pro-
grammed individually from the master unit
directly or as a complete group.
n The cabled remote control (accessory) can be
used for user-specific operation of an individual
slave unit.
Implementation
n The addresses for the master and slave units
are assigned by configuring the cabled remote
control (see separate installation instructions).
9
12
8
13 14
1110
ALARM
ALARM
0-10V
ON/OFF
GND
A
B
JP1
9
12
8
13 14
1110
ALARM
ALARM
0-10V
ON/OFF
GND
A
B
JP1
9
12
8
13 14
1110
ALARM
ALARM
0-10V
ON/OFF
GND
A
B
JP1
9
12
8
13 14
1110
ALARM
ALARM
0-10V
ON/OFF
GND
A
B
JP1
9
12
8
13 14
1110
ALARM
ALARM
0-10V
ON/OFF
GND
A
B
JP1
Fig. 36: Internal network wiring diagram
43
43


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO WLT-EC serie at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO WLT-EC serie in the language / languages: English as an attachment in your email.

The manual is 6,3 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO WLT-EC serie

REMKO WLT-EC serie User Manual - German - 60 pages

REMKO WLT-EC serie User Manual - Dutch - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info