726826
36
Zoom out
Zoom in
Previous page
1/60
Next page
6.2 Condensate drainage
connection
If the temperature falls below the dew point, con-
densate will form on the cooling fins during cooling
mode. Below the heat exchanger is a collection
tray which must be connected to a drain.
n The condensate drainage line should have an
incline of min. 2%. This is the responsibility of
the customer
. If necessary, fit vapour-diffusion-
proof insulation.
n Route the unit's condensate drainage line
freely into the drain line. If the condensate runs
directly into a sewer pipe, fit a trap to prevent
any unpleasant odours.
n When operating the unit at outside tempera-
tures below 0 °C, ensure the condensate
drainage line is laid to protect it against frost. If
necessary, fit a pipe heater.
n Following installation, check that the conden-
sate run off is unobstructed and ensure that the
line is durably leak tight.
min. 2%
Fig. 31: Condensate drainage connection
The condensate hose is designed to be connected
on the left-hand side (as viewed from the front),
although it can also be changed by reconnecting
the hose if necessary
.
6.3 Leak testing
The leak test is carried out after the connection
has been made.
1. Flush the system twice with tap water
.
2. Clean the sieve insert on the dirt trap.
3. Fill the system with water again and bleed
the unit at the manual bleed valves.
4. Adjust the test pressure to at least 200 kPa
(2.0 bar).
5. Check the connections after a period of at
least 24 hours for leaking water
. If water is
visible, the connection has not been estab-
lished properly. Tighten the connection or
establish a new connection.
6. After a successful leak test, remove the
excess pressure from the medium piping if a
water-glycol mixture is used or adjust the
non-circulating pressure to the required
system pressure.
NOTICE!
During manual bleeding, any glycol mixtures
which escape must be disposed of separately
.
Do not feed them into the condensate tray!
1
1: Manual bleeding valve
REMKO WLT EC series
36
36


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO WLT-EC serie at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO WLT-EC serie in the language / languages: English as an attachment in your email.

The manual is 6,3 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO WLT-EC serie

REMKO WLT-EC serie User Manual - German - 60 pages

REMKO WLT-EC serie User Manual - Dutch - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info