6 Installation
6.1 Unit installation
Unit installation
NOTICE!
Installation and commissioning should only be
performed by trained specialists.
The unit is attached by means of a wall bracket,
with consideration to the minimum clearances
required.
1. Mark the mounting points on the structurally
permissible building sections according to the
dimensions of the wall bracket.
2. If necessary
, remove the break out opening
of the housing.
3. Connect the medium pipes, electrical cables
and condensate drainage line to the indoor
unit as described below
.
4. Hang the indoor unit onto the wall bracket by
tilting it back slightly and by pressing the
bottom part of the unit against the bracket.
5. Check again that the unit is level.
Fig. 30: Horizontal positioning
Connection of the medium piping
n The medium piping of the unit is designed
without any transition. The respective transition
(press fitting, soldering sleeve, etc.) can be
selected on an individual basis.
n For the purpose of servicing, connections must
be equipped with shut-of
f valves and the
medium flow rate adjusted using valves for
hydronic balancing.
n Additional automatic bleed valves are to be
provided in the supply and return flow at the
installation’s highest point.
n The medium piping may not exert any struc-
tural load on the unit.
n The line connections may not generate any
thermal or mechanical stresses on the unit. If
necessary cool the piping or support with the
second tool.
Necessary system components
Valve assembly (standard equipment)
With 2-conductor systems cold or warm medium is
fed through the register in the unit and then cold or
warm air is released. Regulation is realised by the
3-way valve assembly
. It comprises the electrically
actuated valve head and the valve body. If the
head is electrically activated, it actuates the body,
which routes the medium into the register. If the
temperature is reached, the head is switched off
and the medium is fed past the heat exchanger
through the bypass .
The bypass serves to ensure the minimum medium
flow rate for the chiller. In the case of units with 2-
way valve, no bypass is present. This version is
recommended with the use of a proportional pres-
sure-controlled circulation pump.
The time between being fully open and fully
closed can be approx. three minutes.
Valves for hydronic balancing
The calculated individual pressure losses in the
pipeline network layout for each individual unit are
adjusted to the entire system with hydronic bal-
ancing valves to be provided by the customer
. The
nominal flow rates for the medium adjust to the
values needed as a consequence of the pressure
loss.
REMKO WLT EC series
34
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO WLT-EC serie at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO WLT-EC serie in the language / languages: English as an attachment in your email.

The manual is 6,3 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO WLT-EC serie

REMKO WLT-EC serie User Manual - German - 60 pages

REMKO WLT-EC serie User Manual - Dutch - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info