Troubleshooting and customer service
The equipment and components are manufactured using state-of-the-art production methods and tested several
times to verify their correct function. If malfunctions should occur, please check the functions as detailed in the
list below. Please inform your dealer if the unit is still not working correctly after all the functional checks have
been performed!
Fault Possible cause Checks Remedial measures
The unit does not start or
switches itself off.
Power outage, undervoltage,
defective mains fuse / main circuit
breaker switched off
Are all electrical installations func-
tioning correctly?
Check the voltage and if necessary
wait for it to come back on
Damaged mains cable
Are all electrical installations func-
tioning correctly?
Repair by specialist
Waiting time after switch-on too
short
Have approx. 5 minutes
elapsed since the restart?
Schedule longer waiting times
Temperate outside operating
temperature range
Are the fans in the indoor unit
and outside component working
correctly?
Take into account the temperature
range for the indoor unit and
outside component
Overvoltages caused by thunder
storms
Has there recently been lightning?
Switch off the mains protection
and switch it back on / have it
checked by a specialist
Fault in external condensation
pump
Did the pump shut down due to
a fault?
Check and if necessary clean the
pump
The unit does not respond to
the remote control.
Transmission distance too far /
receiver affected by interference
Does the indoor unit beep when
pressing a button?
Reduce the distance to less than 6
m or change position
Defective remote control
Is the unit running in manual
mode?
Replace the remote control
Receiver or transmitter unit ex-
posed to excessive solar radiation
Does it function correctly in the
shade?
Place the receiver&transmitter unit
in the shade
Electromagnetic fields are interfer-
ing with transmission
Does it function when switching off
possible sources of interference?
Signal is not transmitted when in-
terference sources are operational
Button in remote control jammed /
two buttons pressed at same time
Does the “Send” symbol appear
on the display?
Release the button / only press
one button
Batteries in remote control are flat
Have new batteries been inserted?
Is the display incomplete?
Insert new batteries
The unit is running but only
provides reduced cooling or
heating performance.
Filter is unclean / air inlet / outlet
blocked by foreign items
Have the filters been cleaned? Clean the filters
Doors and windows open.
Heating/cooling output increases
Have modifications been made to
the building?
Close windows and doors / install
additional units
Neither cooling nor heating mode
has been set
Is the cooling/heating symbol
shown on the display?
Correct the settings for the unit
Fins on outdoor component
blocked by foreign items
Is the fan on the outdoor com-
ponent running ?Are the fins
unobstructed?
Check the fan or winter controller,
reduce the air resistance
Leaking refrigerant circuit
Are there signs of frost on the fins
of the indoor unit?
Repair by specialist
Condensation is leaking out of
the unit.
Drainage pipe on collection
container clogged / damaged
Can the condensation drain off
without any obstruction?
Clean the drainage pipe and
collection container
Faulty external condensation
pump or float
Is the condensation tray full and
the pump running?
Call out a specialist to replace the
pump
Condensation has not drained
away and has collected in the
condensation pipe
Is there a steady fall on the
condensation pipe? Check there is
no blockage in the pipe.
The condensation pipe must have a
fall. If necessary, clean the pipe
Condensation does not drain off
Are the condensation pipes
unblocked and is there a steady fall?
Are the condensation pump and
float switch functioning correctly?
The condensation pipe must have a
fall. If necessary, clean the pipe.
A faulty condensation pump and
float switch should be replaced.
Float is stuck or jammed due to
excessive dirt.
Are the LEDs on the receiver unit
of the indoor unit flashing?
Should be cleaned by specialist
firm.
Malfunction
15
15


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO SV521 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO SV521 in the language / languages: English as an attachment in your email.

The manual is 3,15 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO SV521

REMKO SV521 User Manual - German - 32 pages

REMKO SV521 User Manual - Dutch - 32 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info