The unit runs but condensate
is not formed:
Check the room temperature
The operating range of the unit
is between 6 °C and 32 °C
Check the humidity of the air
Min. 40 % RH required
Check the intake grill and air
filter for contamination
Clean or replace if required!
Have the heat exchanger fins
checked for contamination
This work requires the unit to
be opened and must therefore
only be carried out by an
authorised specialist company!
Check that the compressor is
functioning correctly. If it is not
operational while the fan is run-
ning, then the leakage control
device has disabled the com-
pressor. Check the refrigerant
system for leaks.
Electrical wiring diagram
NOTE
If the unit fails to function
correctly after the checks have
been carried out, contact an
authorised specialist.
Note on refrigerants
The units work with
environmentally-friendly
and ozone-neutral R290
refrigerant.
The mixture of refrigerant
and oil within the unit must
be disposed of properly
in accordance with the
statutory or locally-applicable
regulations.
The unit is loud or
condensate runs out:
Check whether the unit is on
a stable and even base
Check whether the unit is
standing upright and stably
Have the condensate trap or
the connection nozzles checked
to see whether there are dirt
deposits on them
This work requires the unit to
be opened and must therefore
only be carried out by an
authorised specialist company!
Work on the refrigerant
system and on the electrical
equipment must only be
conducted by a specially-
authorised specialist!
! CAUTION
230V~50Hz
L N
PE
Compressor
Condenser
Condenser
OLP
BLACK
Fan
CN1
CN2
CN3 CN4
Temperature
probe
Operating board
Humidity probe
FUSE
P3
P4
P9
T1AL 250V
P5
P12
P1
2-way
solenoid
valve
Microswitch
WHITE
WHITE
BLUEBLUE
BLUE
BLUE
BLUE
BLUE
RED
GREEN/YELLOW
BROWN
RED
Condenser
21


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO SERIE ETF 320 ECO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO SERIE ETF 320 ECO in the language / languages: English as an attachment in your email.

The manual is 2.94 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO SERIE ETF 320 ECO

REMKO SERIE ETF 320 ECO User Manual - German - 28 pages

REMKO SERIE ETF 320 ECO User Manual - Dutch - 28 pages

REMKO SERIE ETF 320 ECO User Manual - French - 28 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info