The units are factory filled with
dry nitrogen to check for leaks.
The pressurised nitrogen is
released when the union nuts
are loosened.
!
CAUTION
Connecting the refrigerant pipes
The on-site connection of the
refrigerant pipes is carried out on
the right side of the units.
It may be necessary to fit
a reducer or flared adapter to the
indoor unit. These fittings are
included with the indoor unit as
an accessory kit. Once installed,
the connections must be insulated
to prevent vapour diffusion.
Refrigerant pipe
Deburrer
6 Deburring the refrigerant pipe
Unit installation
Wall installation
The unit is attached by means of
a wall bracket, taking account of
the air outlet side located towards
the top of the unit.
Ceiling installation
The unit is attached by means
of the integrated ceiling bracket,
taking account of the air outlet
side, which is located on the front
of the unit.
1. Mark the mounting points on
the structurally permissible
building sections according
to the dimensions of the wall
bracket.
2. Remove the housing's break
out opening if necessary.
3. Hook the unit on to the
previously attached bracket.
4. Connect the refrigerant pipes,
electrical cables and condensate
line to the indoor unit as
described below.
5. Check again that the unit is level.
1. Mark the mounting points on
the structurally permissible
building sections according to
the dimensions of the ceiling
bracket.
2. Remove the housing's break
out opening if necessary.
3. Hook the unit onto the four
previously installed screws/
threaded rods.
4. Fit the unit such that it is
attached 5 mm lower in the
connection area (air intake)
than on the air outlet side!
5. Connect the refrigerant
pipes, electrical cables and
condensation pipe to the indoor
unit as described below.
3. Before flanging the refrigerant
pipes, ensure that the union nut
is fitted on the pipe.
4. Prepare the refrigerant pipes as
shown below (Fig. 6+7).
5. Verify that the shape of the
flange is correct (Fig. 8).
6. First connect and hand-tighten
the refrigerant connections
to ensure they are correctly
seated.
7. Now fully tighten the fittings
using 2 suitably sized open-
ended spanners. Use one
spanner to counter the force
when tightening the fitting
(Fig. 9).
8. Use only diffusion-tight
insulation hoses designed for
this temperature range.
9. Route the refrigerant pipes from
the indoor unit to the outdoor
component. Ensure that they
are adequately fastened and
take measures for the oil return,
if necessary!
The following instructions describe
the installation of the refrigerant
circuit and the assembly of the
indoor unit and the outdoor
component.
1.
The required pipe diameters are
given in the table "Technical
data".
2. Remove the factory-fitted
protective caps and union nuts
on the connections and use
these during installation.
19
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO RXT521 DC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO RXT521 DC in the language / languages: English as an attachment in your email.

The manual is 3,38 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO RXT521 DC

REMKO RXT521 DC User Manual - German - 52 pages

REMKO RXT521 DC User Manual - French - 56 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info