Malfunction Possible causes Checks Remedial measures
The unit is running but
only provides reduced or
no cooling or heating
capacity
Filter is dirty / air inlet /
outlet opening is blocked
by debris
Have the filters been
cleaned?
Clean the filters
Windows and doors
open. Heating / cooling
load has increased
Have structural / usage
modifications been
made?
Close windows and
doors / install additional
units
Neither cooling nor
heating mode has been
set
Does the cooling symbol
appear on the display?
Correct the settings for
the unit
Fins on outdoor unit
blocked by foreign
objects
Is the fan on the outdoor
component running? Are
the fins unobstructed?
Check the fan or winter
fan speed control,
reduce the air resistance
Leaking cooling cycle Are there signs of frost
on the exchanger fins of
the indoor unit?
Repair by specialist
Outdoor unit iced up Check outdoor unit. Has
the cassette probe on
the outdoor unit been
correctly positioned?
De-ice and fit the probe
at the point where the
most ice forms
Condensate discharge
on unit
Drainage pipe on collec-
tion container clogged /
damaged
Can the condensate
drain of
f without any
obstruction?
Clean the drainage pipe
and collection container
Faulty external conden-
sate pump or float
Is the collection tray full
of water and the pump
not running?
Call out a specialist to
replace the pump
Condensate has not
drained away and has
collected in the conden-
sate drainage line
Is there an incline on the
condensate drainage
line? Check there is no
blockage in the pipe.
Route the condensate
drainage line with an
incline and clean
Condensate does not
drain of
f
Are the condensate
drainage lines unblocked
and is there a steady
incline? Are the conden-
sate pump and liquid
level switch functioning
correctly?
Route the condensate
drainage line with an
incline and clean it. If the
liquid level switch or the
condensate pump is
defective, have them
replaced
Float is stuck or jammed
due to excessive dirt
Are the LEDs on the
receiver unit of the
indoor unit flashing?
Should be cleaned by
specialist firm
NOTE
If the outdoor unit makes noises at low outside temperatures, even although it is switched off, this is not a
malfunction. This is the winding of the compressor being run briefly in order to heat up the oil within it and
also to guarantee the viscosity at low ambient temperatures. If you do not use the unit in the winter then
you can switch off the breaker
. Switch it back on again at least 12 hours before the next time that the unit
will be required!
47
47


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO RXT 525 DC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO RXT 525 DC in the language / languages: English as an attachment in your email.

The manual is 4,89 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO RXT 525 DC

REMKO RXT 525 DC User Manual - German - 84 pages

REMKO RXT 525 DC User Manual - Dutch - 84 pages

REMKO RXT 525 DC User Manual - French - 84 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info