16
REMKO PGT (E) series
Fault code table
Red flashing code
of the signal lamp
Alarm at
terminal 10
Possible cause
2 x flashing ON
No flame formation at the end of the safety time (TSA)
- defective or dirty fuel valves
- defective or dirty flame sensor
- poor burner setting, no fuel
- defective ignition device
3 x flashing ON
Air pressure alarm error - Air pressure failure after specified time (t10)
has lapsed
- Air pressure alarm frozen in resting position - Error with leakage control
(only in conjunction with LDU11...)
4 x flashing ON External light with the burner start
5 x flashing ON
Air pressure alarm time monitoring
- Air pressure alarm frozen in working position
6 x flashing ON Free
7 x flashing ON
Loss of flame during operation too frequent (repetition limiting)
- defective or dirty fuel valves
- defective or dirty flame sensor
- poor burner setting
8 x flashing ON Free
9 x flashing ON Free
10 x flashing OFF Wiring error or internal error, output contacts, other error
14 x flashing ON CPI contact not closed
Troubleshooting diagnostics
After an unchangeable fault
shutdown, the red signal lamp
lights up. In this condition, it is
possible to press the unlock key
>3 seconds to activate the visual
troubleshooting diagnostics
in accordance with the fault code
table.
Pressing the unlock key again
>3 seconds activates the interface
diagnostics. If interface diagnostics
is activated inadvertently, which
is apparent from the weak red
flickering light in the signal lamp,
pressing the unlock key once more
>3 seconds switches this off again.
The correct switching moment is
signalled by a yellow light pulse.
16


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO PGT 60E at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO PGT 60E in the language / languages: English as an attachment in your email.

The manual is 1,79 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO PGT 60E

REMKO PGT 60E User Manual - German - 28 pages

REMKO PGT 60E User Manual - Dutch - 24 pages

REMKO PGT 60E User Manual - French - 28 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info