NOTICE!
If condensate is removed via a duct in accord-
ance with DIN EN 1717, ensure that any micro-
biological contamination present on the waste-
water side (bacteria, fungi, viruses) cannot
enter the unit connected to it.
8 Electrical wiring
8.1 General notes
A protected power supply cable is to be connected
from the outdoor unit to the indoor unit, and a pro-
tected three-core control line is to be connected to
the indoor unit respectively
.
DANGER!
All electrical installation work is to be performed
by specialist companies. Disconnect the power
supply when connecting the electrical terminals.
NOTICE!
The electrical connection for the units must be
made at a separate feedpoint with a residual
current device in accordance with local regula-
tions and should be laid out by an electrician.
n W
e recommend that a main/repair switch be
installed close to the unit. This must be pro-
vided by the customer.
n The terminal blocks for making the connections
are located at the rear of the unit. When the
unit is installed, measurements can be made
from the front by removing the cover.
n If an optional condensate pump is used as an
accessory in conjunction with the unit, it may
be necessary to install an additional relay with
a higher contact rating after the switch-off con-
tact on the pump to switch off the compressor.
The control line to the outdoor unit contains data
cables which serve to realise the communication
between the indoor unit and the outdoor unit. This
is used for controlling the cooling and heating
capacity and for forwarding alarm codes to the
indoor unit.
Make the connection as follows:
1. Open the unit cover
.
2. Loosen the covers on the right side using a
cross screwdriver
. (Fig. 18).
3. The connection options for the power supply
and control lines are located under the cover
.
4. Connect the control line provided by the cus-
tomer to the terminals P
,Q and E.
5. Connect the control line provided by the cus-
tomer to the indoor units and outdoor unit in
a professional manner (also terminals P
, Q
and E). If the installed indoor unit is the last
one in the connection sequence, the 120
Ohm resistor supplied must be installed
between the terminals P and Q.
6. Then close of
f the cover and the unit cover.
Fig. 18: Connecting the indoor unit
1: Cover
2: Strain relief
3: Terminal block for control line
4: Control line from outdoor unit
REMKO MVW series
26
26


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO MVW 452 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO MVW 452 in the language / languages: English as an attachment in your email.

The manual is 3,45 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO MVW 452

REMKO MVW 452 User Manual - German - 48 pages

REMKO MVW 452 User Manual - Dutch - 48 pages

REMKO MVW 452 User Manual - French - 48 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info