Minimum clearances
The following illustration indicates
the minimum clearances for
trouble-free operation of the
equipment.
The protective zones serve to
provide unhindered air intake and
discharge, as well as providing
sufficient room for performing
maintenance and repairs and
preventing the unit from being
damaged.
Oil return measures
If the outdoor unit is installed at a
higher level than the indoor unit,
suitable oil return measures must
be taken. Usually an oil pump
bend is installed for every 2.5 me-
tres of height difference.
Installation
NOTE
Installation should only be
performed by authorised
specialists.
The following instructions describe
the installation of the refrigerant
circuit and the assembly of the
indoor unit and outdoor unit.
1. The required pipe diameters are
given in the table "Technical
data" for the outdoor unit.
2. Install the indoor unit can
connect the refrigerant pipes as
described in the manual for the
indoor unit.
3. Observe the permitted bending
radius for the refrigerant pipes
during installation. Never bend
a pipe twice in the same place.
Brittle pipes and potential
cracking are the consequences.
Minimum clearances
Oil return measures
Outdoor unit
Oil pump bend
in suction pipe to
outdoor unit
1 x every 2.5
metres of rising
pipe
Radius:
min. 50 mm
max. 15 m
Indoor unit
MVT 600 DC
MVT 900 DC-
1050 DC
A 100 mm 200 mm
B 1,200 mm 1,500 mm
C 600 mm 600 mm
D 150 mm 150 mm
E 600 mm 500 mm
4. To bend the copper tubing, use
the appropriate bending tool to
prevent kinks in the tubing.
5. Lay the refrigerant pipes from
the indoor unit to the outdoor
unit.
In doing so, ensure adequate
fastenings and and take
measures for the oil return!
6. Use the wall or floor brackets
to fit the outdoor unit against
structural parts approved to
support the static load.
Observe the installation
instructions for the brackets.
7. Ensure that structure-borne
sound is not transferred to parts
of the building.
Use vibration dampers to
reduce the effects of structure-
borne sound!
8. Remove the factory-fitted
protective caps and union nuts
on the stop valve connections.
These should be used during
installation.
9. Before flanging the refrigerant
pipes, ensure that the union nut
is fitted on the pipe.
10.Prepare the laid refrigerant
pipes.
(Page 12, figures 5+6)
.
11.
Verify that the shape of the
flange is correct
(
Page 12,
figure 7).
E
D
C
A
Air outlet
Air intake
B
REMKO MVT
14
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO MVT950 DC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO MVT950 DC in the language / languages: English as an attachment in your email.

The manual is 1,43 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO MVT950 DC

REMKO MVT950 DC User Manual - German - 28 pages

REMKO MVT950 DC User Manual - German - 28 pages

REMKO MVT950 DC User Manual - Dutch - 28 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info