Error P5: Excessive temperature on condenser
The unit stops if the refrigerant temperature on the condenser outlet exceeds 65 °C. It re-starts once the
temperature is 52 °C.
Excessive tempera-
ture safety shut-
down. The unit
shows P5.
NO
Check the electrical
connection between
the condenser out-
let's temperature
probe and the
board. Is it OK?
NO
Establish the connection correctly.
YES
YES
Check the temperature probe's resistance
(for resistances, see the table). Is it OK?
YES
NO
Is the refrigerant
temperature on the
condenser outlet
higher than 65°C?
Replace the temper-
ature probe.
YES
Is the outside tem-
perature higher than
50°C?
YES
Switch the unit off.
NO
Is the condenser fan
running properly?
NO
See troubleshooting
for malfunction E8
YES
Is the condenser
dirty?
YES
Clean the con-
denser
.
NO
Is the refrigerant
volume correct?
YES
Replace the control
board
47
47


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO MVT 1053 DC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO MVT 1053 DC in the language / languages: English as an attachment in your email.

The manual is 4,22 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO MVT 1053 DC

REMKO MVT 1053 DC User Manual - German - 78 pages

REMKO MVT 1053 DC User Manual - Dutch - 68 pages

REMKO MVT 1053 DC User Manual - French - 68 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info