726601
26
Zoom out
Zoom in
Previous page
1/48
Next page
7 Condensate drainage
connection and safe
drainage
n The condensate drainage line should have an
incline of min. 2%. This is the responsibility of
the customer
. If necessary, fit vapour-diffusion-
proof insulation.
n If the level of the condensate drainage line on
the unit is above that of the outlet, route the
pipe vertically upwards and then with an incline
to the drain.
n Route the unit's condensate drainage line
freely into the drain line. If the condensate runs
directly into a sewer pipe, fit a trap to prevent
any unpleasant odours.
n When operating the unit at outside tempera-
tures below 4 °C, ensure the condensate
drainage line is laid to protect it against frost. If
necessary, fit a pipe heater.
n Following installation, check that the conden-
sate run off is unobstructed and ensure that the
line is durably leak tight.
Condensate drainage connection
If the temperature falls below the dew point, con-
densate will form on the cooling fins during cooling
mode. A collection tray together with a condensate
pump and liquid level switch are fitted as standard
below the cooling fins. If the liquid level switch trips
a protective shutdown due to inadequate removal
of the condensate, the pump will switch on immedi-
ately and run on for approx. three minutes.
Safe drainage in the event of leakages
Local regulations or environmental laws, for
example the German W
ater Resource Act (WHG),
can require suitable precautions to protect against
uncontrolled drainage in case of leakage to provide
for safe disposal of escaping air conditioning fluid
or hazardous media.
NOTICE!
The maximum capacity of the condensate
pump is 500 mm WS. External influences, such
as air-side back pressure, contamination, or
wear may cause a reduction in performance. To
ensure safe operation function, we recommend
a maximum conveyor height of 450 mm should
not be exceeded!
NOTICE!
If condensate is removed via a duct in accord-
ance with DIN EN 1717, ensure that any micro-
biological contamination present on the waste-
water side (bacteria, fungi, viruses) cannot
enter the unit connected to it.
A
C
B
D
Fig. 15: Condensate drainage connection - incor-
rect!
A: Riser pipe too far away
B: Condensate drainage line too large/small
C: No incline
D: Cannot freely drain away
16-20 mm
min. 2%
max.
500 mmWS
Fig. 16: Condensate drainage connection - correct!
REMKO MVD series
26
26


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO MVD 222 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO MVD 222 in the language / languages: English as an attachment in your email.

The manual is 3,52 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO MVD 222

REMKO MVD 222 User Manual - German - 48 pages

REMKO MVD 222 User Manual - Dutch - 48 pages

REMKO MVD 222 User Manual - French - 48 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info