Function test of the cooling and heating modes
1. Remove the protective caps from the valves.
2. Start the commissioning procedure by briefly
opening the shut-of
f valves on the outdoor
unit until the pressure gauge indicates a
pressure of approx. 2 bar.
3. Check all connections for leaks with leak
detection spray and suitable leak detectors.
4. If no leaks are found, fully open the shut-of
f
valves by turning them anti-clockwise using a
spanner. If leaks are found, remedy the faulty
connection. It is imperative that the vacuum
creation and drying steps are repeated.
5. Activate the main circuit breaker or fuse (to
be provided by the customer).
6. Press the test knob on the outdoor unit and
wait until a frequency of min. 50 Hz is estab-
lished.
7. Use the remote control to switch on the unit
and select the cooling mode, maximum fan
speed and lowest target temperature.
8. Check the overheating, outside, inside, outlet
and vaporisation temperatures and record
the measured values in the commissioning
report. Check the correct function and set-
tings of all regulation, control and safety
devices.
9. Check the unit control system using the func-
tions described in the chapter "Operation".
T
imer, temperature setting, fan speeds and
switching to ventilation or dehumidification
mode.
10. Check the correct function of the condensate
drainage by pouring distilled water into the
condensate tray
. A bottle with a spout is rec-
ommended for pouring the water into the
condensation tray.
11. Switch the indoor unit to heating mode.
12. During the test run, check the functionality of
all of the previously described safety devices.
13. Record the measured values into the com-
missioning report and familiarise the operator
with the system.
14. Remove the pressure gauge. Check that
seals have been fitted in the sealing caps.
15. Re-install all disassembled parts.
43
43


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO ML 685 DC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO ML 685 DC in the language / languages: English as an attachment in your email.

The manual is 3,53 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO ML 685 DC

REMKO ML 685 DC User Manual - German - 68 pages

REMKO ML 685 DC User Manual - Dutch - 68 pages

REMKO ML 685 DC User Manual - French - 72 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info