587984
34
Zoom out
Zoom in
Previous page
1/60
Next page
Measurement tem-
perature
Sensor resistance value
NTC 103 AT
-20 67770 Ω
-15 53410 Ω
-10 42470 Ω
-5 33900 Ω
0 27280 Ω
+5 22050 Ω
+10 17960 Ω
+15 14690 Ω
+20 12090 Ω
+25 10000 Ω
+30 8313 Ω
+35 6940 Ω
+40 5827 Ω
+45 4911 Ω
+50 4160 Ω
+55 3536 Ω
+60 3020 Ω
+65 2588 Ω
+70 2228 Ω
+75 1924 Ω
+80 1668 Ω
+85 1451 Ω
+90 1266 Ω
+95 1108 Ω
+100 973 Ω
Differential pressure monitor
FL medium circuit
The differential pressure monitor
is installed in the medium circuit
in parallel with the evaporator. It
measures the pressure difference
between the input and output
pressure and switches off the unit
when the minimum volume flow
rate is undershot or in case of ex-
tremely high volume flow rates.
Medium circuit PS pressure switch
The pressure switch is located only
in units with storage tanks. This
switch monitors the medium pres-
sure.
Thermal contacts
Condenser fans TX
The thermal contacts of the con-
denser fans prevent an overheat-
ing of the motors.
Thermal contact of circulation
pump QM
The thermal contact is located
inside the circulation pump and
limits its coil temperature.
Phase sequence relay KA3
The phase sequence relay moni-
tors the direction of rotation of the
power supply. In case of an incor-
rect direction of rotation, regula-
tion is not enabled.
Winter fan control, fan control
board FCS1
Using a modulating output volt-
age, the speed of the condenser
fan can be adapted to the con-
densation temperature and thus
a minimum noise level can be
observed.
The IPro controller determines the
current condensation temperature
on the condenser using the high-
pressure transducer. The set value
is then regulated using the fan
control board.
Medium inlet sensor B1
The sensor is located in the me-
dium inlet (system return) of the
unit.
It is used to record the current
actual temperature to regulate the
set value.
Medium outlet sensor B2
The sensor is located in the me-
dium outlet (system inlet flow) of
the unit.
It is used to record the current ac-
tual temperature and monitor the
anti-frost protection temperature.
Fan control sensor B3
The sensor is located on the capac-
itor of the cooling circuit. It is used
to record the current condensation
temperature in cooling mode for
low-noise fan control.
REMKO KWG
34
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO KWG850 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO KWG850 in the language / languages: English as an attachment in your email.

The manual is 7,1 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO KWG850

REMKO KWG850 User Manual - German - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info