587983
26
Zoom out
Zoom in
Previous page
1/60
Next page
Medium lines
The medium lines can be designed
as copper, steel, or plastic pipes.
To minimise pressure losses, only
fittings that are favourable to flow
should be used.
During design, the large volume
flow rates of cold water systems,
higher pressure losses due to a
water/glycol mixtures, and the
minimum volume flow rate of the
chiller must be taken into consid-
eration.
The line must be insulated in a
vapour-diffusion-tight manner, and
any current, local energy savings
ordinances must be observed. UV
resistance must be implemented
outdoors.
Victaulic connectors
The connection to the unit is
implemented using Victaulic con-
nectors. The Victaulic connectors
offer many advantages, such as
vibration reduction of the internal
pipeline at the connection to the
on-site pipework. The pipe adapter
allows a welded or threaded con-
nection to the on-site pipework.
The connection can be seen in the
following figures:
Victaulic connectors
Pressure and temperature indica-
tors
The pressure and temperature in-
dicators to be installed in the inlet
and outlet on site are used to set
the medium volume flow rate. The
indicators should be lockable.
The chiller contains temperature
sensors in the medium inlet, me-
dium outlet, and condenser. Using
the controller, the sensor values
can be queried.
Line regulating valves
Using line regulating valves
provided on site, the individual
pressure losses calculated in the
pipe network design are adapted
to each individual unit in the
overall system. Due to the pressure
loss, the nominal volume flow
rates of the medium are adapted
to the required values. If necessary,
a line regulating valve is required
in the inlet flow line to regulate the
volume flow rate in case the pump
pressure is too high.
Connection of the medium
lines
The on-site connection of the
lines takes place on the rear of
the units.
For servicing purposes, the
connections must be equipped
with shut-off valves and the
volume flow rate must be set
using line regulating valve.
Additional automatic bleeding
valves are provided in the inlet
flow, return, and highest point
of the installation.
The medium lines must not
exert static loads on the unit.
The connection of the lines
must not generate thermal or
mechanical stress on the unit.
Cool the line if necessary and/
or dolly with a second tool.
If the unit is initially operated
with only part of the overall
system, the medium volume
flow rate of the missing parts of
the system must be simulated
using line regulating valves.
The pipe dimensioning must be
designed in such a way that the
required minimum volume flow
rate is not undershot.
Pipe routing
KWP 400-1750
No pipe routing
possible
Free pipe
routing
possible
In order for the minimum
volume flow rate to be
reached, a permanent, high
volume flow rate must be
guaranteed.
!
ATTENTION
Source: Victaulic
REMKO KWG
26
26


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO KWG750 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO KWG750 in the language / languages: English as an attachment in your email.

The manual is 7,1 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO KWG750

REMKO KWG750 User Manual - German - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info