Malfunction
Fault Code Possible cause Check Remedy
The unit
does not
start or
switches
itself off
autono-
mously
Power failure
Is all other electrical equipment
functioning?
Check the voltage and wait for
reactivation.
Unit fuse / main disconnecter
switched off
Does the unit have power?
Switch on the unit fuse / main
switch.
Waiting period too short Is the compr. symbol flashing?
Plan for a longer waiting
period.
C(n)Mn
The maintenance interval
of compressor (n) has been
reached
Have the compressor mainte-
nance performed by a specialist
company
Reset the operating hours after
the maintenance interval.
AEP(n)
The maintenance interval of
the circulation pump has been
reached
Have the circulation pump
maintenance performed by a
specialist company
Reset the operating hours after
the maintenance interval.
APS /
ASPh
Incorrect electrical direction of
rotation of the mains supply
Has the phase sequence relay
switched through?
Change the direction of rota-
tion.
StbY
The controller is in standby
mode
Does the compressor symbol
light up?
Apply voltage and
select the operating mode.
Return temperature or param-
eter setting incorrect
Check the setting. Change the settings.
OFF No fault
Is the "external enable" ena-
bling contact closed?
Close / open
contact used.
AP1 Defective sensor, medium inlet Check of resistor PB1 Replace the defective sensor.
AP2
Defective sensor, medium
outlet
Check of resistor PB2 Replace the defective sensor.
AP 3-6 Defective transm. condensation Check of transmitter PB Replace the defective transmit..
AP
Defective sensor, outdoor tem-
perature
Check of resistor PB Replace the defective sensor.
Atr1
Cabled remote control not con-
nected
Check of the connection / line
of the cabled remote control
If missing, set Parameter CF 74
from "1" to "0"
b(n)HP
High-pressure fault
Circuit n
Are the fans rotating?
Is the air inlet of the condenser
free of objects?
Have it checked by
a specialist company.
b(n)LP
Low-pressure fault
Circuit n
Is the pressure in the cooling
circuit OK?
Have it checked by
a specialist company.
b(n)hP Overtemperature of condenser
Are the fans rotating?
Is the air inlet of the condenser
free of objects?
Have it checked by
a specialist company.
b(n)hP
Undertemperature of condenser
Circuit n
Have the operating tempera-
tures been exceeded?
Decommission the system.
b(n)AC
b(n)AH
Anti-frost protection has
reacted
Circuit n
Is the temperature of the inlet
flow 4°C or lower?
Increase the return temperature,
increase the medium volume
flow rate
.
AEFL
Differential pressure monitor /
flow monitor
reacted
Are the following items OK:
- Medium volume flow rate
- No air in the medium
lines
- Circulation pump capacity
- Switches the differential pres-
sure /
flow monitor
- Shut-off valves open
- Medium pressure too low
Have it checked by
a specialist company.
Atr1
Cabled remote control not
configured or connected
Does the cabled remote control
function perfectly?
Have the remote control and/
or parameters checked by a
specialist company.
AEt1,
b(n)tF,
A(n)tr,
b(n)HP
APS /
ASPh
Control fuse F1 230V triggered Has fuse F1 triggered?
Have the fuse replaced by a
specialist company.
19
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO KWG600 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO KWG600 in the language / languages: English as an attachment in your email.

The manual is 7,1 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO KWG600

REMKO KWG600 User Manual - German - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info