10 Leak testing
The leak test is carried out after the connection
has been made.
1. Flush the system twice with tap water
.
2. Clean the sieve insert on the dirt trap.
3. Fill the system with water again and bleed
the unit at the manual bleed valves.
4. Adjust the test pressure to at least 200 kPa
(2.0 bar).
5. Check the connections after a period of at
least 24 hours for leaking water
. If water is
visible, the connection has not been estab-
lished properly. Tighten the connection or
establish a new connection.
6. After a successful leak test, remove the
excess pressure from the medium piping if a
water-glycol mixture is used or adjust the
non-circulating pressure to the required
system pressure.
11 Before commissioning
Anti-freeze protection for the medium
If a water-glycol mixture is used, it is to be pre-
mixed before being put in the system. The desired
concentration is then to be checked.
Bleeding the system
n Air may still be in the pipe lines after the leak
testing. This is carried during operation of the
circulation pump to the automatic bleeding
valves or to the cold water drain. It is neces-
sary to bleed again here.
n The non-circulating pressure must then be
adjusted to the required system pressure.
1
Fig. 49: Manual bleeding
1: Manual bleeding
NOTICE!
During manual bleeding, any glycol mixtures
which escape must be disposed of separately
.
Do not feed them into the condensate tray!
Diaphragm expansion vessel
n The preliminary pressure for the diaphragm
expansion vessel must be adjusted individually
to the system layout, the volume of the medium
and the installation site.
Valves for hydronic balancing
n The calculated excess pressure in the pipe net-
work layout at the individual cold water outlets
must be adjusted with the hydronic balancing
valves.
39
39


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO KWD serie 25-35-45-55-70-85-100 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO KWD serie 25-35-45-55-70-85-100 in the language / languages: English as an attachment in your email.

The manual is 4,47 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO KWD serie 25-35-45-55-70-85-100

REMKO KWD serie 25-35-45-55-70-85-100 User Manual - German - 52 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info