587908
34
Zoom out
Zoom in
Previous page
1/44
Next page
34
REMKO GPM
Unit without temperature control
For replacing the gas valve, the
CO2 and if necessary the offset
value must be adjusted.
- Start the burner and after swit-
ching on the fan bring the burner
to “maximum output” by pres-
sing and holding the reset button
on the rear of the unit for 2 to 3
seconds.
Operation at maximum output is
indicated by the green LED on the
front of the unit flashing once.
After about two minutes, connect
a gas analyser and read off the
CO2 value.
Compare this value with the values
in the “Gas settings” table for the
type of gas used.
- If the value is outside the spe-
cified range, it can be corrected
with the CO2 regulating screw
on the Venturi tube:
The gas flow rate and accordingly
the CO2 value decrease when the
screw is tightened.
The CO2 value increases when the
screw is unscrewed.
Subsequently set the burner to
“minimum output” by pressing
and holding the reset button again
for 2 to 3 seconds.
Operation at “minimum output” is
indicated by the green LED rapidly
flashing twice.
- Wait until the minimum out-
put at the burner has stabilised
and check that the CO2 value
is equal to or slightly below the
CO2 value at the maximum flow
rate ( up to -0.3%).
A deviating value can be corrected
with the offset screw.
To make changes to values, un-
screw the metal plug and turn the
regulating screw:
The CO2 value decreases when
the screw is unscrewed.
The CO2 value increases when the
screw is tightened.
After making any adjustments with
the offset regulating screw, the
CO2 value at maximum output
must be rechecked by carrying out
the above described steps.
After carrying out these steps, set
the unit to “normal” mode by
pressing and holding the reset but-
ton again for 2 to 3 seconds.
This mode is indicated by the
green LED showing a steady light.
This also occurs when the mains
supply to the unit is disconnected
and reconnected.
Unit with temperature control
For replacing the gas valve, the
CO2 and if necessary the offset
value must be adjusted.
- Adjust the regulating parameters
of the sensor NTC1 (“REG SAN”
on the temperature control) to
a value that is higher than the
value measured by the sensor
NTC1 (“FLOW VL” on the tem-
perature control).
- Switch on the burner.
The burner will reach maximum
output after about two minutes
after starting.
Connect an exhaust gas analy-
ser and read off the CO2 value.
Compare this value with the “gas
settings” (page 32) for the type of
gas used.
- If the value is outside the spe-
cified range, it can be corrected
with the CO2 regulating screw
on the Venturi tube.
The gas flow rate and accordingly
the CO2 value decrease when the
screw is tightened.
The CO2 value increases when the
screw is unscrewed.
Subsequently set the burner to
minimum output by adjusting the
REG SAN value to a value that is
lower than the measured tempe-
rature.
- Wait until the minimum out-
put at the burner has stabilised
and check that the CO2 value
is equal to or slightly below the
CO2 value at the maximum flow
rate ( up to -0.3%).
A deviating value can be corrected
with the offset screw.
To make changes to values, un-
screw the metal plug and turn the
regulating screw:
The CO2 value decreases when
the screw is unscrewed.
The CO2 value increases when the
screw is tightened.
After making any adjustments with
the offset regulating screw, the
CO2 value at maximum output
must be rechecked by carrying out
the above described steps.
Replacing the gas valve and CO2 and offset regulator
We reserve the right to make changes to dimensions and design in the interest of technological advances.
If the unit is not set to
“normal mode“, the control
board will automatically re-
set the unit after 20 minutes.
NOTE
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO GPM 55 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO GPM 55 in the language / languages: English as an attachment in your email.

The manual is 4,39 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO GPM 55

REMKO GPM 55 User Manual - German - 44 pages

REMKO GPM 55 User Manual - Dutch - 44 pages

REMKO GPM 55 User Manual - French - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info