Check the electrodes for correct
seating (see diagram).
It is important that the monitoring
electrode [IO] is located tangential
to the ignition burner head and is
not located within the same.
The ignition electrode [Z] must
discharge towards the outside
edge of the ignition burner at
an adequate distance to the
monitoring electrode.
2) Checking the chimney and
supply air pipes
Visually inspect all pipes and
connecting pieces.
Any dirt deposits that have
accumulated on the end piece
of the supply air pipe must be
removed.
3) Checking and cleaning the
Venturi tube
Remove dirt deposits at the
entrance of the Venturi tube with a
brush or other suitable implement.
Ensure that no dirt falls in to the
Venturi tube.
4) Checking the gas supply
pressure
Ensure that the pressure upstream
of the gas valve corresponds to the
value prescribed for the respective
type of gas.
This check must be carried out
with the unit switched on at
maximum output.
5) Checking the fl ame monitoring
device
With the unit in heating mode,
close the gas valve and ensure that
fault F1 is indicated. Open the gas
valve again, reset and wait for the
unit to restart.
6) Checking the safety
thermostat(s)
This check must be carried out
with the unit operating in heating
mode.
- Heat the thermostat sensor using
a hot air gun or similar until fault
F2 is indicated.
- Allow the thermostat sensor(s) to
cool down and reset the unit.
- This check must be carried out on
all thermostats in the unit.
Maintenance
2-3 mm
Z
IO
In order to ensure maximum
performance and a long service
life of the units, several checks
must be made once a year and in
any event before the start of the
heating season.
1) Check the condition of the
ignition and monitoring
electrodes as well as that of the
ignition gas burner.
2) Check the condition of the
supply air and chimney pipes as
well as the end pieces.
3) Check the Venturi tube for
clogging.
4) Check the heat exchanger for
fouling.
5) Check the gas pressure
upstream of the gas valve.
6) Check the function of the fl ame
monitoring device.
7) Check the safety thermostat(s).
8) Check the ionisation fl ow (> 2
microamperes)
1) Checking the electrodes
Dismantle the ignition burner
completely and clean the gas
system and gas nozzle with
compressed air.
Check the ceramic coating on the
electrodes for intactness.
Carefully remove any oxide
deposits on the metal part of the
electrodes with a very fi ne emery
cloth.
For steps 1, 2, 3 and 4, the
mains and gas supply to
the unit must always be
interrupted.
Steps 5, 6, 7 and 8 are carried
out with the unit in heating
mode.
NOTE
We reserve the right to make changes to dimensions and design in the interest of technological advances.
s
s
s
31


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO GPM 15 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO GPM 15 in the language / languages: English as an attachment in your email.

The manual is 4,39 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO GPM 15

REMKO GPM 15 User Manual - German - 44 pages

REMKO GPM 15 User Manual - Dutch - 44 pages

REMKO GPM 15 User Manual - French - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info