REMKO GPM
Room correction
For this function, use of the
temperature control ATR.6 is
necessary.
A type of function is described
in the following that enables
maximum energy efficiency to
be achieved by the hot air heater
assisted by the control electronics
and temperature control.
In order to activate the ambient
correction function, the parameter
[C1]
param k 11 must be set to 1.
The purpose of the room
correction function is to ensure
rapid heating at the beginning and
subsequently maintain the room
temperature at a constant level.
In this way, not only can layer
formation in the room air be
reduced, but also the fuel demand
reduced in particular.
The two correction reference
values are the temperature
measured by the sensor NTC2
(in the temperature control) and
the circulation air temperature
measured by the sensor NTC1 (at
the unit).
To activate the function, set the
parameter
param k 17 to 1.
When the room temperature
approaches the setpoint value,
the modulation temperature is
changed linearly based on the two
parameters A16 and A24.
This makes it possible to operate
the unit on heat demand
at maximum output and to
quickly reach the preset room
temperature.
The heat output is subsequently
reduced which increases the
efficiency of the unit and the room
is heated with less hot air.
This enables the layer formation in
the room air and simultaneously
the heat loss to be reduced.
The units are supplied with the
following factory settings:
Modulation temperature:
„REG SAN“ 22°C
Neutral correction range:
A24 2°C
Correction coefficient:
A16 2
The parameter A24 determines
the range within which the
room temperature is corrected.
The parameter A16 offers the
possibility to increase the efficiency
of the temperature reduction
to the setpoint “REG SAN” as
shown on the graph. At the
standard setting, the modulation
temperature on reaching the room
temperature corresponds to:
„REG SAN“ =
24°C-(2°C x 2.5) = 19°C
The correction is independent of
the set room temperature.
The graph shows the room
temperatures [ST2] in relation
to the installation height of the
units „REG SAN“ during the initial
heating phase.
To deactivate the correction, set
the parameter [C1]
param k 11 to
0.
When deactivating the correction,
the value “REG SAN” must be
correctly regulated in order to
avoid the following conditions:
- „REG SAN“ adjusted too high:
Strong layer formation with
high heat loss in roof area and
increased energy demand as a
consequence.
-
„REG SAN“ adjusted too low:
Time to reach the required room
temperature too long.
With correction deactivated, adjust
“REG SAN” so that the value is
higher than ST2 by the difference
in metres between the room and
modulation sensor multiplied by
0.4/0.5°C.
To change the modulation value
“REG SAN” on the temperature
control and to change all specified
values, see further back in the
manual.
Raumtemperatur
Modulationstemperatur
ST1
ST2
A24
A24 x A16
ST1 Korrektur
ST1
ST2
0,5h 1h 1,5h 2h 2,5h 3h
Modulation temperature
Room temperature
ST1 correction
10


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO GPM 15 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO GPM 15 in the language / languages: English as an attachment in your email.

The manual is 4,39 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO GPM 15

REMKO GPM 15 User Manual - German - 44 pages

REMKO GPM 15 User Manual - Dutch - 44 pages

REMKO GPM 15 User Manual - French - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info