REMKO series ETF Eco
Remove any potential ignition
sources
Leaking refrigerant in combina-
tion with corresponding ignition
sources can lead to an explo-
sion. All ignition sources must
therefore be kept away from
the working area at all times!
This also includes the smoking
of cigarettes. Inform all persons
present that this includes the
axing of safety notes and the
closing o of the working area.
Sucient ventilation
Before starting work, ensure that
the working area is outdoors
or has sucient ventilation. A
continuous ventilation stream
is required while working. The
safety of the persons working
must be guaranteed by the ex-
haust air equipment: potentially
leaking refrigerant must be lead
away safely and drained into the
atmosphere in an optimum man-
ner.
Checking the refrigerant circuit
If electronic components need
to be replaced, ensure that
the spare parts have the same
function and identical technical
specications. The maintenance
and replacement regulations of
the manufacturer must always
be observed and complied with.
Please contact the support of the
manufacturer with any problems
or queries. The following safety
checks must be carried out when
using combustible refrigerants:
- The ll level adjusts to the size
of the rooms in which the unit is
located.
- The exhaust air equipment and
its outlets function properly and
are not blocked or obstructed.
Checking the electronic compo-
nents
A component and safety check
must be carried out before
repairing and maintaining
electronic components. If safety
cannot be ensured due to a de-
fect on a component, installation
must not take place until safety
can be guaranteed again. If the
defect on the spare part cannot
be remedied and downtime of
the unit is no longer acceptable,
an adequate temporary solution
must be arranged. The owner/
operator of the unit must be in-
formed about this. The detailed
safety check must include the
following aspects:
- Capacitors are discharged. Dis-
charging must be done in a safe
process to prevent ying sparks.
- There must be no electronic
components active or uninsu-
lated wires while lling, repairing
or cleaning.
- There must be no earthing of
the system.
Repairs to closed components
Before repairing closed compo-
nents/housing parts, the unit
must be free from voltage. If
carrying out the repairs free from
voltage cannot be avoided, the
critical points of potential refrig-
erant leakages must be checked
using a leak detector.
The following notes must be
observed when working on elec-
tronic components if the hous-
ing is changed in such a way that
its safety is inuenced. This also
relates to cases where the lines
are damaged, there is excessive
or incorrect pin assignment, con-
nections are not assigned in the
original way or similar deviations
to the expected condition are
determined.
Repairing of intrinsically safe
components
Do not introduce permanent
inductive or capacitive loads
into the existing circuits without
ensuring that the maximum
permitted voltages and amper-
ages of the assemblies and lines
are not exceeded. Intrinsically
safe components are individual
components that can be operat-
ed in the presence of ammable
substances. The test equipment
must be adjusted according to
the situation-dependent condi-
tions. Only use components
which are ocially approved by
the manufacturer as spare parts.
Unapproved components can
cause a re in the event of a leak-
age in the refrigerant circuit.
10


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO ETF-460 Eco at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO ETF-460 Eco in the language / languages: English as an attachment in your email.

The manual is 3.28 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO ETF-460 Eco

REMKO ETF-460 Eco User Manual - German - 28 pages

REMKO ETF-460 Eco User Manual - Dutch - 28 pages

REMKO ETF-460 Eco User Manual - French - 28 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info