Configuratie - Vervolg
Omschrijving Waardebereik Fabrieksinstelling Beschrijving
WE BUS 00-05 05
•00 = Relais (schakelende warmtegenerator).
•01 = CAN-BUS (Cascade schakelend).
•02 = eBUS (warmtegenerator zonder temperatuurregeling,
voorgeschreven modulatiegraad, cascade modulerend).
•03 = eBUS (warmtegenerator met temperatuurregeling,
voorgeschreven richttemperatuur, T-WE Richt).
•04 = 0-10V (voorgeschreven richttemperatuur T-WE Richt,
branderrelais worden parallel aangestuurd).
Alleen bij regelingstype 01, 02, 03, 07.
Sensor 08 moet zijn aangesloten.
•05 = 0-10V (voorgeschreven modulatiegraad).
Alleen bij de regeling van het type 02 of 06.
WE 2 Type
(Uitgang A7
Vrijgave koelen)
00-22 08
Niet actief bij warmtegenerator 1 met tweetraps brander.
•00 = geen tweede warmtegenerator.
•01 = Eéntraps warmtegenerator (schakelend).
•07 = Warmtepomp.
•08 = Koelen 1.
•09 = Koelen 2.
•20 = Vastebrandstofketel (extra niet regelbare
warmtegenerator).
•21 = Combi-pomp
•22 = Pomp voor warmtegenerator 1 (bijv. extra
warmtegenerator bij cascades).
WE 2 Buffer
00-03 00
Alleen actief als warmtegenerator 2Type als vastebrandstof-
ketel is geselecteerd.
Aanloopontlasting:
AAN: T-WE 2 > Min T-WE 2.
UIT: T-WE 2 < [Min T-WE 2-5K].
•00 = Verwarmen op combi (geen reservoir) [Voeler 08].
AAN: T-WE 2 > [T-Combi+Hyst Brander 2+5K].
UIT: T-WE 2 < [T-Combi+Hyst Brander 2].
•01 = Verwarmen op bufferreservoir [Voeler 01, 03].
AAN: T-WE 2 > [T-buffer B+Hyst Brander 2+5K].
UIT: T-WE 2 < [T-Buffer O+Hyst Brander 2].
•02 = Verwarmen op WW-reservoir [Voeler 06].
AAN: T-WE 2 > [T-WW+Hyst Brander 2+5K].
UIT: T-WE 2 < [T-WW+Hyst Brander 2].
•03 = Verwarmen op reservoir 3 (zwembad) [Voeler 15].
AAN: T-WE 2 > [T-reservoir 3+Hyst Brander 2+5K].
UIT: T-WE 2 < [T-reservoir 3+Hyst Brander 2].
Niveau 4 - SPECIALIST - Beschrijving van de parameters en instelwaarden - Vervolg
27
27


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO CMF160 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO CMF160 in the language / languages: Dutch as an attachment in your email.

The manual is 3,34 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info