587578
19
Zoom out
Zoom in
Previous page
1/36
Next page
Regelung,Sicherheitsregelung und Widerstände
Sensor Heißgas, Sensor IPM AT
Kompressor AT
Kompressorregelung durch Heißgastemperatur Kompressorregelung durch Verdampfertemp.
Kompressorregelung durch Verdampfertemp.
Kompressorregelung durch Stromaufnahme
Kompressorregelung durch Umgebungstemperatur
Kompressorregelung durch Umgebungstemperatur
Sensor Verflüssiger AT,Sensor Umgebungstemp. AT
Sensor Verdampfer IT, Sensor Umluft IT
Temp.
Widerstand
0 160,73 kΩ
5 125,57 kΩ
10 98,78 kΩ
15 78,23 kΩ
20 62,35 kΩ
25 50,00 kΩ
30 40,33 kΩ
Heißgastemperatur
Regelung
< 87°C
normaler Betriebszustand,
Regelung über IT
93°C-97°C kein Änderung der Frequenz
97°C-110°C
absenkung der Frequenz 1Hz/3sek.
> 110°C
Abschaltung Kompressor
Oberflächentem-
peratur IT
Regelung Kühlen
> 6°C
normaler Betriebszustand,
Regelung über IT
< 6°C kein Änderung der Frequenz
< 4°C Absenkung der Frequenz 1Hz/3sek.
< 1°C Abschaltung Kompressor
Oberflächentem-
peratur IT
Regelung Heizen
< 51°C
normaler Betriebszustand,
Regelung über IT
51°C-55°C kein Änderung der Frequenz
55°C-65°C Absenkung der Frequenz 1Hz/3sek.
> 65°C Abschaltung Kompressor
Stromaufnahme
Regelung Kühlen/Heizen
> 6,1 A kein Änderung der Frequenz
6,2-6,7A Absenkung der Frequenz 1Hz/3sek.
6,7-7,5 Abschaltung Kompressor
Umgebungstemperatur
Regelung Kühlbetrieb
>53°C Frequenz 32 Hz
47°C-53°C Frequenz 50 Hz
39°C-47°C Frequenz 70 Hz.
15°C-39°C
normaler Betriebszustand,
Regelung über IT
<15°C Frequenz 32 Hz
Umgebungstemperatur
Regelung Heizbetrieb
>23°C Frequenz 32 Hz
19°C-23°C Frequenz 50 Hz
12°C-19°C Frequenz 70 Hz.
<12°C
normaler Betriebszustand,
Regelung über IT
<-25°C oder >+70°C Abschaltung Kompressor
Temp.
Widerstand Messpunkt
20 0,71 Ω
U-V
V-W
U-W
Temp.
Widerstand
0 27,42 kΩ
5 22,15kΩ
10 18,00 kΩ
15 14,72 kΩ
20 12,10 kΩ
25 10,00 kΩ
30 8,31 kΩ
19
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO ATY261 DC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO ATY261 DC in the language / languages: German as an attachment in your email.

The manual is 4,45 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO ATY261 DC

REMKO ATY261 DC User Manual - English - 36 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info