Function test of cooling operating mode
1. Remove the protective caps from the valves.
2. Start the commissioning procedure by briefly
opening the shut-of
f valves on the outdoor
unit until the pressure gauge indicates a
pressure of approx. 2 bar.
3. Check all connections for leaks with leak
detection spray and suitable leak detectors.
4. If no leaks are found, fully open the shut-of
f
valves by turning them anti-clockwise using a
spanner. If leaks are found, remedy the faulty
connection. It is imperative that the vacuum
creation and drying steps are repeated.
5. Switch on the main circuit breaker or fuse.
6. Use the remote control to switch on the unit
and select the cooling mode, maximum fan
speed and lowest target temperature.
7. Measure and record all the required values in
the commissioning report and check the
safety functions.
8. Check the unit control system using the func-
tions described in the chapter "Operation".
T
imer, temperature setting, fan speeds and
switching to recirculation or dehumidifying
mode.
9. Check the correct function of the condensate
drainage line by pouring distilled water into
the condensate tray
. A bottle with a spout is
recommended for pouring the water into the
condensate tray.
10. Switch the indoor unit to cooling mode.
Due to the turn on delay
, the compressor will
start up a few minutes later.
11. Check all regulating, control and safety
devices for function and correct adjustment
during the test run.
12. Check the control of the indoor unit with the
functions described in the operating instruc-
tions (timer
, temperature adjustments and all
mode settings).
13. Measure the overheating, outside, internal,
outlet and evaporator temperatures and
record the test data in the commissioning log.
14. Remove the pressure gauge and install the
caps
Final tasks
n Re-install all disassembled parts.
n Familiarise the operator with the system.
REMKO ATY series
40
40


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO ATY 266 DC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO ATY 266 DC in the language / languages: English as an attachment in your email.

The manual is 3,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO ATY 266 DC

REMKO ATY 266 DC User Manual - German - 64 pages

REMKO ATY 266 DC User Manual - Dutch - 64 pages

REMKO ATY 266 DC User Manual - French - 68 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info