Series AMT 40-E AMT 55-E AMT 80-E AMT 110-E
Working area temperature
°C 3-32 3-32 3-32 3-32
Working area humidity
% relative
humidity
40-100 40-100 40-100 40-100
Max. dehumidification output
l/day 38 55 80 107
at 30°C/80 r. h.
l/day (DER) 32,1 (2,38)) 48,0 (2,27) 69,6 (2,69) 93,1 (2,38)
at 20 °C/70 r. h.
l/day (DER) 15,4 (1,46) 29,8 (1,94) 39,2 (1,99) 54,9 (1,88)
at 10 °C/60 r. h.
l/day (DER) 5,3 (0,61) 6,9 (0,58) 10,8 (0,68) 16,8 (0,71)
Max. air volume flow m
3
/h 290 430 800 1200
Condensate tank capacity litre 8/7 18/16 18/16 without
Compressor
Design Rotating piston Rotating piston Rotating piston Rotating piston
Refrigerant R134a R407c R407c R407c
Refrigerant quantity kg 0,45 0,55 0,65 1,55
Voltage supply
V/Hz 230/1~/50
Max. rated power consumption A 2,8 4,0 4,9 7,2
Max. power consumption kW 0,58 0,90 1,10 1,70
at 20 °C / 70 % r. h.
kW 0,44 0,64 0,82 1,22
Fuse protection (on site)
A 16 16 16 16
Noise pressure level L
pA
1m
1)
dB(A) 58 60 63 67
Depth mm 490 530 535 605
Width
mm 480 605 605 710
Height mm 640 705 790 895
Height incl. transport handle mm 935
Weight
kg 34 43 47 65
EDP no. 612400 612550 612800 612900
(DER) = dehumidification performance coefficient according to DIN EN 810
1) Noise measurement DIN 45635 - 13 - Category 3
We reserve the right to make changes in dimensions and design in the interest of technical advances.
Technical data
23