805747
61
Zoom out
Zoom in
Previous page
1/88
Next page
Code Display text Description Solution
E.00.16 DHW sensor Open Domestic Hot Water tank tempera
ture sensor is either removed or
measures a temperature below
range
Calorifier sensor open:
Bad connection: check the wiring and connec
tors
Faulty sensor: replace the sensor
E.00.17 DHW sensor Closed Domestic Hot Water tank tempera
ture sensor is either shorted or
measures a temperature above
range
Calorifier sensor short-circuited:
Bad connection: check the wiring and connec
tors
Faulty sensor: replace the sensor
E.00.44 TcombiDhwOutOpen Domestic hot water outlet tempera
ture sensor is either removed or
measures a temperature below
range
DHW temperature sensor open:
Bad connection: check the wiring and connec
tors
Faulty sensor: replace the sensor
E.00.45 DHWoutSens shorted Domestic hot water outlet tempera
ture sensor is either shorted or
measures a temperature above
range
DHW temperature sensor short-circuited:
Bad connection: check the wiring and connec
tors
Faulty sensor: replace the sensor
E.01.04 5x Flame Loss Error 5x Error of unintended Flame Loss
occurance
Flame loss occurs 5 times:
Vent the gas supply to remove air
Check that the gas valve is fully opened
Check the gas supply pressure
Check the operation and setting of the gas
valve unit
Check that the air supply inlet and flue gas out
let are not blocked
Check that there is no recirculation of flue
gases
E.01.11 Fan Out Of Range Fan speed has exceeded normal op
erating range
Fan fault:
Bad connection: check the wiring and connec
tors.
Faulty fan: replace the fan
Fan operates when it should not be operating:
check for excessive chimney draught
E.01.12 Return Higher Flow Return tempearture has a higher
temperature value than the flow tem
perature
Flow and return reversed:
Bad connection: check the wiring and connec
tors
Water circulation in wrong direction: check the
circulation (direction, pump, valves)
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Malfunctioning sensor: check the Ohmic value
of the sensor
Faulty sensor: replace the sensor
E.01.24 Combustion Error Several combustion errors occurs
with 24 hours
Low ionisation current:
Vent the gas supply to remove air.
Check that the gas valve is fully opened.
Check the gas supply pressure.
Check the operation and setting of the gas
valve unit.
Check that the air supply inlet and flue gas out
let are not blocked.
Check that there is no recirculation of flue
gases.
E.02.13 Blocking Input Blocking Input of the Control Unit
from device external environment
Blocking input is active:
External cause: remove external cause
Wrong parameter set: check the parameters
10 Troubleshooting
7684359 - v.11 - 13122021 61
61


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Quinta Ace 55 - T-Control at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Quinta Ace 55 - T-Control in the language / languages: English as an attachment in your email.

The manual is 4.19 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info