The boiler has a blocking input. A potential-free contact can be connected
to the BL terminals of the connector. If the contact is opened, the boiler will
be blocked.
Change the function of the input using parameter AP001. This parameter
has the following 3 configuration options:
Complete blocking: no frost protection with the outdoor sensor and no
boiler frost protection (pump does not start and burner does not start)
Partial blocking: boiler frost protection (pump starts when the
temperature of the heat exchanger is < 6°C and the burner starts when
the temperature of the heat exchanger is < 3°C)
Lock out: no frost protection with outdoor sensor and partial boiler frost
protection (pump starts when the temperature of the heat exchanger is <
6°C, the burner does not start when the temperature of the heat
exchanger is < 3°C).
Release input
Caution
Only suitable for potential-free contacts (dry contact).
The boiler has a release input. A potential-free contact can be connected
to the RL terminals of the connector.
If the contact is closed during a heat demand, the boiler will be blocked
immediately.
If the contact is closed when there is no heat demand, the contact does
nothing until the main PCB receives a ‘start burner’- command. After that
command, a waiting time starts. If the contact is closed during this
waiting time, the burner does not start and the boiler will be blocked. Set
the waiting time with parameter AP008. A waiting time of 0 will disable
the contact.
Connecting an outdoor sensor
An outdoor sensor can be connected to the Tout connector. In the case of
an on/off thermostat, the boiler will control the temperature with the set
point from the internal heating curve. An OpenTherm controller can also
use this outdoor sensor. In that case, the desired internal heating curve
must be set on the controller.
Use below mentioned sensors, or sensors with identical characteristics.
Set parameter AP056 to the installed outdoor sensor type.
AF60 = NTC 470 Ω/25°C
QAC34 = NTC 1000 Ω/25°C
1. Connect the plug from the outdoor sensor to the Tout connector.
Frost protection combined with outdoor sensor
The central heating system can also be protected against frost in
combination with an outdoor sensor. The radiator valve in the frost-
sensitive room must be open.
Fig.25 Blocking input
AD-3000972-02
BL
Fig.26 Release input
AD-3001303-02
RL
Fig.27 Connecting an outdoor sensor
AD-3000973-02
Tout
5 Installation
7684359 - v.11 - 13122021 27
27


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Quinta Ace 55 - T-Control at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Quinta Ace 55 - T-Control in the language / languages: English as an attachment in your email.

The manual is 4.19 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info