Code Display text Description Solution
E.04.06 Max Flue temp Measured flue temperature above
limit
-
E.04.07 TFlow Sensor Deviation in flow sensor 1 and flow
sensor 2 detected
Flow temperature sensor deviation:
Bad connection: check the connection
Faulty sensor: replace the sensor
E.04.08 Safety input Safety input is open Air pressure differential switch activated:
Bad connection: check the wiring and connec
tors
Pressure in flue gas duct is or was too high:
Non-return valve does not open
Siphon blocked or empty
Check that the air supply inlet and flue gas
outlet are not blocked
Check the cleanliness of the heat exchanger
E.04.09 TFlue Sensor Deviation in flue sensor 1 and flue
sensor 2 detected
Flue gas temperature sensor deviation:
Bad connection: check the connection
Faulty sensor: replace the sensor
E.04.10 Unsuccessful start 5 Unsuccessful burners starts detec
ted
Five failed burner starts:
No ignition spark:
Check the wiring between the CU-GH and
the ignition transformer
Check the ionisation/ignition electrode
Check breakdown to earth
Check the condition of the burner cover
Check the earthing
Replace the CU-GH
Ignition spark but no flame:
Vent the gas pipes to remove air
Check that the air supply inlet and flue gas
outlet are not blocked
Check that the gas valve is fully opened
Check the gas supply pressure
Check the operation and setting of the gas
valve unit
Check the wiring on the gas valve unit
Replace the CU-GH
Flame present, but ionisation has failed or is in
adequate:
Check that the gas valve is fully opened
Check the gas supply pressure
Check the ionisation/ignition electrode
Check the earthing
Check the wiring on the ionisation/ignition
electrode.
E.04.11 VPS VPS Gas Valve proving failed Gas leakage control fault:
Bad connection: check the wiring and connec
tors
Gas leakage control VPS faulty: Replace the
valve proving system (VPS)
Gas valve unit faulty: Replace the gas valve
unit
E.04.12 False flame False flame detected before burner
start
False flame signal:
The burner remains very hot: Set the O2
Ionisation current measured but no flame
should be present: check the ionisation/ignition
electrode
Faulty gas valve: replace the gas valve
Faulty ignition transformer: replace the ignition
transformer
10 Troubleshooting
7684359 - v.11 - 13122021 63
63


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Quinta ACE 45 T-Control at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Quinta ACE 45 T-Control in the language / languages: English as an attachment in your email.

The manual is 4.19 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Quinta ACE 45 T-Control

Remeha Quinta ACE 45 T-Control Usermanual and installation guide - German - 116 pages

Remeha Quinta ACE 45 T-Control Usermanual and installation guide - Dutch - 80 pages

Remeha Quinta ACE 45 T-Control Usermanual and installation guide - French - 84 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info