Tab.27 Adjustment for BREEAM with gas type G20 (H gas)
Code Description Display text Range 135 160
DP003 Abs. max fan DHW Maximum fan speed on Domestic Hot Wa
ter
1000 - 8500 Rpm 5900 7000
GP007 Fan RPM Max CH Maximum fan speed during Central Heat
ing mode
1000 - 8500 Rpm 5900 7000
GP008 Fan RPM Min Minimum fan speed during Central Heating
+ Domestic Hot Water mode
900 - 8500 Rpm 1900 1900
GP009 Fan RPM Start Fan speed at appliance start 900 - 5000 Rpm 2200 2200
Tab.28 Adjustment for gas type G30/G31 (butane/propane)
Code Display text Description Range 135 160
DP003 Abs. max fan DHW Maximum fan speed on Domestic Hot Wa
ter
1000 - 8500 Rpm 5450 6400
GP007 Fan RPM Max CH Maximum fan speed during Central Heat
ing mode
1000 - 8500 Rpm 5450 6400
GP008 Fan RPM Min Minimum fan speed during Central Heating
+ Domestic Hot Water mode
900 - 8500 Rpm 2150 2150
GP009 Fan RPM Start Fan speed at appliance start 900 - 5000 Rpm 3000 3000
Tab.29 Adjustment for BREEAM with gas type G30/G31 (butane/propane)
Code Display text Description Range 135 160
DP003 Abs. max fan DHW Maximum fan speed on Domestic Hot Wa
ter
1000 - 8500 Rpm 5800 6850
GP007 Fan RPM Max CH Maximum fan speed during Central Heat
ing mode
1000 - 8500 Rpm 5800 6850
GP008 Fan RPM Min Minimum fan speed during Central Heating
+ Domestic Hot Water mode
900 - 8500 Rpm 2150 2150
GP009 Fan RPM Start Fan speed at appliance start 900 - 5000 Rpm 3000 3000
3. Check the setting of the gas/air ratio.
Important
Make sure to apply the O2 values specified for BREEAM.
7.2.2 Checking/setting combustion
1. Unscrew the cap from the flue gas measuring point.
2. Insert the probe for the flue gas analyser into the measurement
opening.
Warning
During measurement, seal the opening around the sensor fully.
Important
The flue gas analyser must have a minimum accuracy of ±0.25%
O2.
Important
The flue gas analyser must meet the requirements of BS 7927 or
BS-EN 503793 and be calibrated according to the manufacturer's
requirements.
Fig.45 Flue gas measuring point
AD-0000222-01
7 Commissioning
36 7701838 - v.09 - 10122021
36


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Quinta Ace 160 - T Control at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Quinta Ace 160 - T Control in the language / languages: English as an attachment in your email.

The manual is 3.13 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info