805748
43
Zoom out
Zoom in
Previous page
1/76
Next page
Code Display text Description Adjustment range Submenu 135 160
AP074 Force summer
mode
The heating is stopped. Hot water
is maintained. Force Summer
Mode
0 = Off
1 = On
Outdoor
tempera
ture
0 0
AP079 Building Inertia Inertia of the building used for heat
up speed
0 - 255 Outdoor
tempera
ture
0 0
AP080 Frost min out
temp
Outside temperature below which
the antifreeze protection is activa
ted
-32 - 32 °C Outdoor
tempera
ture
0 0
AP102 Boiler Pump
function
Configuration of the boiler pump
as zone pump or system pump
(feed lowloss header)
0 = No
1 = Yes
Commercial
boiler
0 0
AP110 2nd return sen
sor
Parameter to activate the 2nd re
turn sensor
0 = Inactive
1 = Active
Commercial
boiler
0 0
CP000 MaxZoneT
FlowSetpoint
Maximum Flow Temperature set
point zone
0 - 90 °C CH 90 90
CP010 Tflow setpoint
zone
Zone flow temperature setpoint,
used when the zone is set to a
fixed flow setpoint.
0 - 90 °C CH 90 90
CP020 Zone Function Functionality of the zone 0 = Disable
1 = Direct
CH 1 1
CP060 RoomT. Holiday Wished room zone temperature on
holiday period
5 - 20 °C CH 6 6
CP070 MaxReduce
dRoomT.Lim
Max Room Temperature limit of
the circuit in reduced mode, that
allows switching to comfort mode
5 - 30 °C CH 15 15
CP210 Zone HCZP
Comfort
Comfort footpoint of the tempera
ture of heat curve of the circuit
15 - 90 °C CH 15 15
CP220 Zone HCZP Re
duced
Reduced footpoint of the tempera
ture of heat curve of the circuit
15 - 90 °C CH 15 15
CP230 Zone Heating
Curve
Heating curve temperature gradi
ent of the zone
0 - 4 CH 2.5 2.5
CP340 TypeReduced
NightMode
Type of reduced night mode, stop
or maintain heating of circuit
0 = Stop heat demand
1 = Continue heat de
mand
CH 0 0
CP470 Zone screed
drying
Setting of the screed drying pro
gram of the zone
0 - 30 Days CH 0 0
CP480 ScreedStart
Temp
Setting of the start temperature of
the screed drying program of the
zone
20 - 50 °C CH 20 20
CP490 ScreedStop
Temp
Setting of the stop temperature of
the screed drying program of the
zone
20 - 50 °C CH 20 20
CP750 MaxZone Pre
heat time
Maximum zone preheat time 0 - 65000 Min CH 0 0
CP780 Control strategy Selection of the control strategy for
the zone
0 = Automatic
1 = Room Temp. based
2 = Outdoor Temp. based
3 = Outdoor & room
based
CH 1 1
DP003 Abs. max fan
DHW
Maximum fan speed on Domestic
Hot Water
1000 - 8500 Rpm Commercial
boiler
5700 6700
DP010 Hysteresis DHW Temperature hysteresis for the
heat generator to start on domestic
hot water production
0 - 60 °C Commercial
boiler
7 7
DP011 Stop offset
DHW
Temperature offset to stop heat
generator on domestic hot water
production
0 - 60 °C Commercial
boiler
5 5
8 Settings
7701838 - v.09 - 10122021 43
43


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Quinta Ace 135 - T Control at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Quinta Ace 135 - T Control in the language / languages: English as an attachment in your email.

The manual is 3.13 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info