2. Fill the central heating system with clean water, using the filling and
drain valve (½", fitted on the front section).
3. Check the water-side connections for tightness.
4. Power up the boiler.
6.1.2 Filling the siphon
Danger
The siphon must always be sufficiently filled with water. This
prevents flue gases from entering the room.
1. Fill the siphon up to the mark via the condensate collector.
2. Put the sealing cap back on the condensate collector.
6.1.3 Preparing the gas circuit
Warning
Ensure that the boiler is disconnected from the power supply.
1. Open the main gas valve.
2. Open the boiler gas valve.
3. Check the tightness of the gas circuit.
4. Vent the gas supply pipe by unscrewing measuring point P1.
The gas supply pipe is properly vented when a gas smell can be
noticed.
5. Check the gas inlet pressure at measuring point P1.
The advised inlet pressure is shown on the data plate.
Caution
The inlet pressure may never exceed the maximum pressure
mentioned in the technical data table.
6. Tighten the measuring point again.
6.1.4 Setting the gas leakage monitoring (VPS)
When the boiler is equipped with a VPS, it must be set to 50% of the gas
inlet pressure. Proceed as follows:
Fig.74 Filling and drain valve location
AD-3001559-01
Fig.75 Filling the siphon
AD-3001600-01
12
Fig.76 Gas inlet pressure measuring point
AD-3001560-02
P1
6 Preparation of commissioning
7734324 - v.06 - 01102021 43
43


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Gas 320 Ace at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Gas 320 Ace in the language / languages: English as an attachment in your email.

The manual is 6.49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Gas 320 Ace

Remeha Gas 320 Ace Usermanual and installation guide - German - 104 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info