7.2.6 Contrôle du clapet anti-retour
1. Débrancher la conduite d'arrivée d'air du venturi.
2. Dévisser l'écrou borgne du bloc vanne gaz.
3. Débrancher les fiches du ventilateur (sur l'avant et l'arrière).
4. Retirer la fiche à visser du bloc vanne gaz.
5. Retirer la fiche de l'électrode d'allumage du transformateur
d'allumage.
6. Démonter le ventilateur.
7. Retirer le ventilateur et le bloc vanne gaz.
8. Inspecter le clapet anti-retour et le remplacer s'il est défectueux ou
endommagé, ou si le kit de maintenance contient un clapet anti-
retour.
9. Remonter dans l'ordre inverse du démontage.
Fig.37 Débranchement du ventilateur
AD-3001178-01
1
3
4
2
5
Fig.38 Contrôle du clapet anti-retour
AD-3001181-01
2x
6
8
7
9
7 Entretien
7717180 - v02 - 06022019 Calora Tower Gas 41
41


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Calora Tower Gas - 65 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Calora Tower Gas - 65 in the language / languages: French as an attachment in your email.

The manual is 4.66 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Calora Tower Gas - 65

Remeha Calora Tower Gas - 65 Installation Guide - Dutch - 56 pages

Remeha Calora Tower Gas - 65 Installation Guide - French - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info