Système semi-CLV en surpression (C(12)3 parallèle )
LLongueur totale de la gaine d'arrivée d'air et de la buse de fumées
jusqu'à la partie commune
Raccordement de la buse de fumées
Raccordement de l'arrivée d'air
Important
La différence maximale de hauteur tolérée entre l'arrivée de l'air
comburant et la buse de fumées est de 36 m.
Tab.28 Longueur maximale de cheminée (L)
Diamètre 60/100 mm 80/125 mm(1)
Calenta Ace 15s 22 m 40 m(1)
Calenta Ace 25s 12 m 40 m(1)
Calenta Ace 28c 12 m 40 m(1)
Calenta Ace 35s 7 m 40 m
Calenta Ace 40c 6 m 40 m
(1) En conservant la longueur maximale, il est possible d'utiliser des coudes
supplémentaires 5 x 90º ou 10 x 45º.
Tableau de réduction
Tab.29 Réduction du conduit pour chaque élément utilisé (parallèle)
Diamètre 60 mm 80 mm
Coude à 45° 1,1 m(1)
0,9 m(2)
1,2 m
Coude à 90° 3,5 m(1)
3,1 m(2)
4,0 m
(1) Type : C(12)3 parallèle
(2) Type : C(12)3 concentrique et tous les autres types
Tab.30 Réduction du conduit pour chaque élément utilisé (concentrique)
Diamètre 60/100 mm 80/125 mm
Coude à 45° 1,0 m 1,0 m
Coude à 90° 2,0 m 2,0 m
6.5.5 Consignes complémentaires
Installation
Pour installer les conduits d'évacuation des fumées et d'arrivée d'air, se
référer aux instructions du fabricant des matériels correspondants.
Après l'installation, vérifier l'étanchéité de toutes les pièces véhiculant
des fumées et de l'air.
Avertissement
Si les conduits d'évacuation des fumées et d'arrivée d'air ne sont
pas installés conformément aux instructions (par exemple s'ils ne
sont pas étanches, si les supports correspondants ne sont pas
posés correctement, etc.), ils peuvent poser un danger et/ou
entraîner des blessures corporelles.
S'assurer que l'inclinaison du conduit d'évacuation des fumées est
suffisante (au moins 50 mm par mètre) et que le collecteur de
Fig.33 Différentes zones de pression
AD-0001212-01
L = +
6 Installation
40 7688048 - v.03 - 12042019
40


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Calenta Ace 35S at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Calenta Ace 35S in the language / languages: French as an attachment in your email.

The manual is 16.31 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Calenta Ace 35S

Remeha Calenta Ace 35S User Manual - Dutch - 44 pages

Remeha Calenta Ace 35S Installation Guide - Dutch - 140 pages

Remeha Calenta Ace 35S User Manual - French - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info