ESP-LXME Controller
E
The SEEF Actions screen appears, allowing you to set the
controller’s behavior when a SEEF condition exists.
A. Diagnose and Eliminate allows the controller to determine if the
high ow condition is due to a problem on the mainline (broken
pipe, stuck valve, etc) or downstream of one of the valves that
was running when the high ow condition was detected. The
controller will eliminate the high ow condition by closing the
Master Valve to eliminate a mainline problem or closing the
problem valve to eliminate a problem with a station.
B. Shut Down and Alarm instructs the controller to shut down
the Master Valve when a high ow condition is detected. The
controller will not attempt to diagnose if the problem is on the
mainline or downstream of a valve.
C. Alarm Only allows the controller to issue an alarm condition, but
take no other action.
Press the + and – buttons to set the SEEF Action; then press Next.
F
The SELF Settings screen appears with Low Flow Threshold
selected, allowing you to set the bottom limit (between 1-95%)
that a station must achieve to be considered low ow. Press the
+ and – buttons to set the Low Flow Threshold; then press Next.
Press and HOLD buttons to accelerate settings for percentages.
NOTE: Consider using the default setting of 70% (or lower) for
SEEF Low ow Threshold. Using a higher percentage can result in
false alarms due to normal hydraulic variability.
e f
G
Settling Time is selected, allowing you to set the time limit (from
3-10 minutes) that a station ow rate must remain at (or below)
the threshold before the controller will issue an alarm or take
action. Press the + and buttons to set the Settling Time; then
press Next.
H
The SELF Actions screen appears, allowing you to set the
controller’s behavior when a SELF condition exists.
A. Diagnose and Eliminate allows the controller to determine if the
low ow condition is due to a problem on the mainline (aects all
valves) or downstream of one of the valves that was running when
the low ow condition was detected. The controller will eliminate
the low ow condition by closing the Master Valve to eliminate
a mainline problem or closing the problem valve to eliminate a
problem with a station.
B. Shut Down and Alarm instructs the controller to shut down the
Master Valve when a low ow condition is detected. The controller
will not attempt to diagnose if the problem is on the mainline or
downstream of a valve.
C. Alarm Only allows the controller to issue an alarm condition, but
take no other action.
Press the + and – buttons to set the SELF Action; then press Next.
g h
NOTE: If the selected action for both SEEF and SELF is Alarm
Only, then the system is not disabled and the Delay to Re-Enable
screen will not be shown.
67


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for RAINBIRD ESP-LXME Controller at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of RAINBIRD ESP-LXME Controller in the language / languages: English as an attachment in your email.

The manual is 3,43 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of RAINBIRD ESP-LXME Controller

RAINBIRD ESP-LXME Controller Quick start guide - English - 1 pages

RAINBIRD ESP-LXME Controller User Manual - German - 34 pages

RAINBIRD ESP-LXME Controller Quick start guide - Dutch - 1 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info