BASLER MODEL AVC63-4 VOLTAGE REGULATOR
IMPORTANT: The exciter field DC resistance must be 15 Ohms or higher and less than 100 Ohms.
If the exciter field DC resistance is less than 15 Ohms and the full load field current does not exceed the
maximum continuous current rating of the controller, a resistor of ample wattage must be added in series
with the field to increase the total resistance to 15 Ohms.
FREQUENCY COMPENSATION:
The frequency compensation feature improves system load pickup performance by restraining voltage
recovery until the frequency has also started to recover. The corner frequency range is set for 50 Hz or
60 Hz by connecting the Corner Frequency Jumper to the appropriate terminal. The corner frequency
setting is adjusted by the Underfrequency Control potentiometer. Clockwise rotation increases the
corner frequency and Counterclockwise rotation decreases the corner frequency. (Current Version)
OVEREXCITATION SHUTDOWN:
The overexcitation shutdown feature removes controller output power, after a time delay, if the exciter
field voltage exceeds 100V DC, ±5%. The time delay is inversely proportional to the magnitude of the
detected overvoltage – up to 135V DC. Beyond 140V DC, the field voltage is removed after
approximately two seconds. Once the output power is removed, the controller can be reset by decreasing
the input voltage to less than 10V AC for two seconds, minimum. This can be achieved by stopping the
prime mover or by interrupting the controller input power with a reset switch.
SYSTEM START-UP:
Start engine, allow a few minutes to warm-up to operating temperature and rated speed. Generator
voltage should build up. If the voltage does not build up it may be necessary to Field Flash the
generator. (See section on Field Flashing) Slowly adjust the controller’s voltage control potentiometer
until the generator voltage reaches the nominal level. Apply and remove the generator load to verify
stability. If the generator responds too slowly or hunts (oscillates) adjust the controller’s stability control
with no load applied. Also check the stability of the governor system (mechanical or electronic) if
applicable. Next check the regulation under normal operating conditions. If not acceptable, check the
engine speed. Be sure to use an average-sensing voltmeter not an RMS-sensing voltmeter and should be
connected at the same point as the controller sensing. Verify the corner frequency setting by slowly
reducing the generator frequency until the generator output voltage just starts to decrease. If adjustment
of the corner frequency is required, (Current Version) rotate the underfrequency control fully
counterclockwise. Reduce the generator frequency from nominal (either 50Hz or 60 Hz) to the desired
corner frequency. Slowly adjust the underfrequency control clockwise until the generator output voltage
just starts to decrease.
6
58


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for PowerTech PTS-15T-3 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of PowerTech PTS-15T-3 in the language / languages: English as an attachment in your email.

The manual is 7,07 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info