685357
40
Zoom out
Zoom in
Previous page
1/44
Next page
ELECTRICAL CONNECTIONS
ELECTRICAL WIRING
All wiring must be applicable with local electrical codes. A qualified licensed electrician must
perform all electrical wiring connections. Ground Fault (GFCI) breakers must be installed to protect all
vehicle branch circuits. All switches and controls must be securely mounted to prevent damage and
accidental opening or closing from vibration, road shock and vehicle motion.
Battery, load leads and the remote switch panel connections are necessary for completing the
installation. Make final connections to the battery only after all other connections have been made, as this
will prevent unintentional starting. Some specific details on each connection are stated in the following
paragraphs. Refer to the wiring diagram for specific details. All wiring to the generator set shall be securely
supported or harnessed to prevent abrasion. Additional support is required to prevent exposure to the exhaust
system and any possible leakage of fuel, oil, or grease. At least 2 inches of clearance must be maintained
between electrical wiring and hot exhaust parts. Wiring must not be located directly below or close to the
fuel system, oil fill and drain locations.
A separate 12-volt battery is recommended for the generator set. With a separate battery, cables
should be kept short in length thus eliminating problems with excessive voltage drop. See the Table below
for cable size (AWG) to length requirements.
NOTE: IMPORTANT – PTRV-3 Generators DO NOT have 12Vdc battery charging. A separate battery
charging devise must be installed on the vehicle to keep the generator battery charged.
NOTE: A heavy gauge #4 ground strap must be connected between the ground lug on the generator set and
the frame of the vehicle. All wiring connections made at the time of installation should be readily accessible
for periodic inspection and servicing.
DISTANCE BETWEEN
GENERATOR SET AND
BATTERY
CABLE SIZE (AWG) REQUIREMENTS
AT VARIOUS TEMPERATURES
0°F (-18°C) 32°F (0°C) 75°F (24°C)
15’ (4.6M) 2 4 6
10’ (3.0M) 4 6 8
5’ (1.5M) 6 6 8
2.5’ (0.8M) 8 8 8
AC LOAD LEAD CONNECTIONS
Some generator sets have 3 color-coded leads. The Black lead (L1) is hot. The White or Gray lead
(L2) is neutral and the Green lead is ground. The load leads can be routed directly from the junction box to
the vehicle AC circuit or transfer switch connection. All installations require that the load leads be routed
through flexible conduit from the generator end bracket to the junction box location. The
load lead junction box must be accessible for servicing and inspection.
AC load lead (L2) White or Gray is always the neutral lead on PTS generator sets. Make sure the
neutral of the AC circuit in the vehicle is connected to the (L2) White or Gray lead. If equipment ground type
plugs and receptacles (3 prong) are used in the vehicle, the green wire must be connected to the chassis
ground. On vehicles, which also have provisions for using an outside AC, power source, the neutral lead as
well as the Black (L1) hot lead must be completely isolated from the generator set when power is switched to
the outside source.
10
40


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for PowerTech PTRV-3 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of PowerTech PTRV-3 in the language / languages: English as an attachment in your email.

The manual is 1,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info