MARATHON SE350 VOLTAGE REGULATOR
START-UP PROCEDURE:
Ensure the voltage regulator is correctly connected to the generator. Refer to the specific connection
diagram supplied with the generator. Set the regulator voltage adjust to full counter-clockwise
(minimum voltage level). Set the stability control full clockwise (maximum stability level). Connect the
positive lead of a 100V DC voltmeter to F1 and the negative lead of the voltmeter to F2 or use an
appropriate AC voltmeter on the generator output leads.
Start and run the generator at no load and rated speed. The generator voltage should build up to a
minimum level. (Actual level is dependent upon connection). If it does not build up, refer to field
flashing section in generator manual. Slowly adjust the voltage control until the generator voltage
reaches the normal value. Turn the stability adjust counter-clockwise until instability is shown on the
voltmeter. With the system operating in an unstable condition, slowly adjust the stability control
clockwise until generator stability is reached. Interrupt regulator power for a short time (approximately
1-2 seconds). If the generator remains stable no further adjustment is necessary. If the generator does not
remain stable increase the stability slightly and interrupt regulator power again. Repeat this procedure
until system stability is reached and maintained.
TROUBLESHOOTING
SYMPTOM CAUSE ACTION
Residual Voltage
No Output
Residual Voltage at regulator power
input wires 3&4 below 10V AC.
Acceleration time to rated speed too long.
Field leads F1, F2 not connected.
Power input leads not connected.
Blown or missing fuse.
Defective regulator.
Defective generator.
Check wiring diagram for proper
connections.
Flash generator field.
Reduce acceleration time.
Interrupt power input to regulator after
achieving rated speed.
Connect field leads F1, F2.
Connect power input leads 3,4.
Replace fuse.
Replace regulator.
Consult generator manual.
Output Voltage Low Incorrect connections.
Voltage adjust turned down.
Defective regulator.
Check wiring diagram for proper
connections.
Rotate voltage adjust CW until desired
voltage is reached.
Replace regulator.
Output Voltage High Voltage adjust turned too high.
Rotate voltage adjust CCW until desired
voltage is reached.
Output Voltage High
No Adjustment
Defective regulator. Replace regulator.
Generator Output
Voltage Hunting
Stability adjust not set properly. Rotate the stability adjust in a CW
direction until hunting stops.
Poor Regulation Defective regulator. Replace regulator.
24
51


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for PowerTech PT20-ECRR at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of PowerTech PT20-ECRR in the language / languages: English as an attachment in your email.

The manual is 4,84 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info