672280
8
Zoom out
Zoom in
Previous page
1/76
Next page
Operation manual
6
U-5~18MX4 + U-8~16ME4M + U-8~16ME4 + U-4~6ML5
Urban Multi air conditioner
4PW40727-1A
9.2. Maintenance before a long stop period (e.g. at
the end of the season)
Let the indoor units run in fan only operation for about half a day
in order to dry the interior of the units. Refer to "7.1. Cooling,
heating, fan only, and automatic operation" on page 3 for details
on fan only operation.
Tu rn off the power. The remote controller displays disappear.
Clean air filters and casings of indoor units. Refer to the
operation manual supplied with the indoor units for details on
how to proceed and make sure to install cleaned air filters back
in the same position.
10. FOLLOWING SYMPTOMS ARE NOT AIR
CONDITIONER TROUBLES
Symptom 1: The system does not operate
The air conditioner does not start immediately after the ON/OFF
button on the remote controller is pushed.
If the operation lamp lights, the system is in normal condition.
To prevent overloading of the compressor motor, the air
conditioner starts 5 minutes after it is turned ON again in case it
was turned OFF just before. The same starting delay occurs
after the operation mode selector button was used.
If "Centralized Control" is displayed on the remote control and
pressing the operation button causes the display to blink for a
few seconds.
This indicates that the central device is controlling the unit.
The blinking display indicates that the remote control cannot be
used.
The system does not start immediately after the power supply is
turned on.
Wait one minute until the micro computer is prepared for
operation.
Symptom 2: Cool/Heat cannot be changed over
When the display shows " " (change-over under
centralized control), it shows that this is a slave remote
controller.
When the cool/heat changeover remote control switch is
installed and the display shows " " (change-over under
centralized control).
This is because cool/heat changeover is controlled by the cool/
heat changeover remote control switch. Ask your dealer where
the remote control switch is installed.
Symptom 3: Fan operation is possible, but cooling and heating do not
work.
Immediately after the power is turned on.
The micro computer is getting ready to operate. Wait 10
minutes.
Symptom 4: The fan strength does not correspond to the setting.
The fan strength does no change even if the fan strength
adjustment button in pressed.
During heating operation, when the room temperature reaches
the set temperature, the outdoor unit goes off and the indoor unit
changes to whisper fan strength.
This is to prevent cold air blowing directly on occupants of the
room.
The fan strength will not change even if the button is changed,
when another indoor unit is in heating operation.
Symptom 5: The fan direction does not correspond to the setting
The fan direction does not correspond to the remote control
display. The fan direction does not swing.
This is because the unit is being controlled by the micro
computer.
Symptom 6: White mist comes out of a unit
Symptom 6.1: Indoor unit
When humidity is high during cooling operation
If the interior of an indoor unit is extremely contaminated, the
temperature distribution inside a room becomes uneven. It is
necessary to clean the interior of the indoor unit. Ask your dealer
for details on cleaning the unit. This operation requires a
qualified service person.
Immediately after the cooling operation stops and if the room
temperature and humidity are low.
This is because warm refrigerant gas flows back into the indoor
unit and generates steam.
Symptom 6.2: Indoor unit, outdoor unit
When the system is changed over to heating operation after
defrost operation
Moisture generated by defrost becomes steam and is
exhausted.
Symptom 7: The remote controller display reads "U4" or "U5" and stops,
but then restarts after a few minutes
This is because the remote control is intercepting noise from
electric appliances other than the air conditioner. This prevents
communication between the units, causing them to stop.
Operation automatically restarts when the noise ceases.
Symptom 8: Noise of air conditioners
Symptom 8.1: Indoor unit
A "zeen" sound is heard immediately after the power supply is
turned on.
The electronic expansion valve inside an indoor unit starts
working and makes the noise. Its volume will reduce in about
one minute.
A continuous low "shah" sound is heard when the system is in
cooling operation or at a stop
When the drain pump (optional accessories) is in operation, this
noise is heard.
A "pishi-pishi" squeaking sound is heard when the system stops
after heating operation.
Expansion and contraction of plastic parts caused by
temperature change make this noise.
A low "sah", "choro-choro" sound is heard while the indoor unit
is stopped.
When the other indoor unit is in operation, this noise is heard. In
order to prevent oil and refrigerant from remaining in the system,
a small amount of refrigerant is kept flowing.
Symptom 8.2: Indoor unit, outdoor unit
A continuous low hissing sound is heard when the system is in
cooling or defrost operation.
This is the sound of refrigerant gas flowing through both indoor
and outdoor units.
A hissing sound which is heard at the start or immediately after
stopping operation or defrost operation.
This is the noise of refrigerant caused by flow stop or flow
change.
Symptom 8.3: Outdoor unit
When the tone of operating noise changes.
This noise is caused by the change of frequency.
Symptom 9: Dust comes out of the unit
When the unit is used for the first time in a long time.
This is because dust has gotten into the unit.
Symptom 10: The units can give off odours
The unit can absorb the smell of rooms, furniture, cigarettes,
etc., and then emit it again.
Symptom 11: The outdoor unit fan does not spin.
During operation.
The speed of the fan is controlled in order to optimize product
operation.
4PW40727-1A Page 6 Thursday, October 11, 2007 11:02 AM
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Panasonic U-14ME4 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Panasonic U-14ME4 in the language / languages: English, German, Dutch, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 1,9 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info