Installation instructions
for the specialist company
LEVANA 2.0 6 kW
LEVANA 2.0 8 kW
LEVANA AQUA 2.0
ARINA 2.0
INARA 2.0
EN
Exhaust system and chimney design
min. 4000
EN 13384-2
min. 80
min. 80
-P
Fig. 2.13 Exhaust gas connection
Chimney dimensions
The chimney dimensions are in accordance with DIN EN 13384 2
and in accordance with the country-specic regulations.
ARINA 2.0 6 kW / INARA 2.0 6 kW / LEVANA 2.0 6 kW
Nominal heat output .............................................................................. 6.0 kW
Partial heat output ................................................................................... 2.1 kW
Exhaust mass ow .....................................................................................5.5 g/s
Exhaust temperature at the nozzle ..................................................163.0 °C
Minimum pump pressure at nominal heat output ......................11.2 Pa
Minimum pump pressure at partial heat output ..........................10.3 Pa
LEVANA 2.0 8 kW
Nominal heat output .............................................................................. 8.0 kW
Partial heat output ................................................................................... 2.4 kW
Exhaust mass ow .....................................................................................6.0 g/s
Exhaust temperature at the nozzle ..................................................138.0 °C
Minimum pump pressure at nominal heat output ......................12.5 Pa
Minimum pump pressure at partial heat output ............................9.5 Pa
LEVANA AQUA 2.0 8 kW
Nominal heat output .............................................................................. 8.0 kW
Partial heat output ................................................................................... 2.4 kW
Exhaust mass ow .....................................................................................7.1 g/s
Exhaust temperature at the nozzle ...................................................129.4°C
Minimum pump pressure at nominal heat output ......................11.2 Pa
Minimum pump pressure at partial heat output ............................9.1 Pa
Max. permissible water operating pressure ...................................2.5 bar
If the pump pressures are too high (> 20 Pa), then you should set
up pump pressure limitation (e.g. draft regulator in the chimney)!
Set the required pump pressure at the exhaust gas outlet to 0 Pa
for the chimney calculation!
Multiple use of the chimney is possible with special approval
(contact the district master chimney sweep).
The chimney must correspond to a temperature class soot re resist-
ance of at least T400.
Warning! Serious personal injury and environmental
damage owing to hazardous combustion gases!
Combustion gases in the installation room which occur as a
result of a blocked chimney are dangerous. The chimney, con-
nector and flue gas tract must be free from obstructions and
cleaned in accordance with the manufacturers instructions.
Only permitted fuels may be used!
We reserve the right to make technical changes
61
78-4643-2481_R6_LEVANA 2.0_ARINA 2.0_INARA 2.0_DE-EN-FR.indd 6178-4643-2481_R6_LEVANA 2.0_ARINA 2.0_INARA 2.0_DE-EN-FR.indd 61 11.04.2023 14:41:4511.04.2023 14:41:45
61


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Olsberg LEVANA 2.0 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Olsberg LEVANA 2.0 in the language / languages: English, German, French as an attachment in your email.

The manual is 34.97 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info