Information Servicing
(Required for the units adopt R32/R290 Refrigerant only)
11
1. Checks to the area
3. General work area
4. Checking for presence of refrigerant
5. Presence of re extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate
re extinguishing equipment shall be available to hand. Have a dry power or CO2 re extinguisher
adjacent to the charging area.
7. Ventilated area
Ensure that the area is in the open or that it it adequately ventilated before breaking into the system
or conducting any hot work. A degree of ventilation shall continue during the period that the work is
carried out. The ventilation should safely disperse any released refrigerant and preferably expel it
externally into the atmosphere.
8. Checks to the refrigeration equipment
Where electrical components are being changed, they shall be t for the purpose and to the correct
specication. At all times the manufacturer s maintenance and service guidelines shall be followed.
If in doubt consult the manufacturer s technical department for assistance. The following checks shall
be applied to installations using ammable refrigerants:
6. No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe
work that contains or has contained ammable refrigerant shall use any sources of ignition in such a
manner that it may lead to the risk of re or explosion. All possible ignition sources, including cigarette
smoking, should be kept suciently far away from the site of installation, repairing, removing and
disposal, during which ammable refrigerant can possibly be released to the surrounding space. Prior
to work taking place, the area around the equipment is to be surveyed to make sure that there are
no ammable hazards or ignition risks. NO SMOKING signs shall be displayed.
2. Work procedure
All mintenance sta and others working in the local area shall be instructed on the nature of work
being carried out. work in conned sapces shall be avoided. The area around the work space shall
be sectioned o. Ensure that the conditions within the area have been made safe by control of
ammable material.
Prior to beginning work on systems containing ammable refrigerants, safety checks are necessary
to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following
precautions shall be complied with prior to conducting work on the system.
Works shall be undertaken under a controlled procedure so as to minimise the risk of a
ammable gas or vapour being present while the work is being performed.
The area shall be checked with an appropriate refrigerant detector prior to and during work,
to ensure the technician is aware of potentially ammable atmospheres. Ensure that the leak
detection equipment being used is suitable for use with ammable refrigerants, i.e. no sparking,
adequately sealed or intrinsically safe.
,,
,,
,
,
35
133


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Olimpia Splendid UI ALYAS E INVERTER 12 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Olimpia Splendid UI ALYAS E INVERTER 12 in the language / languages: English, Dutch, Italian as an attachment in your email.

The manual is 18,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info